10.3.12Resetting the Parallel Capacity/Redundant System after

EMERGENCY UPM OFF

CAUTION:

Do not attempt to restart the system after Emergency UPM Off until the cause

of the emergency has been identified and cleared.

The Emergency UPM Off PUSH IN TO RESET pushbutton is a small white button on the SSBM Control/Monitor Panel. The PUSH TO RESET pushbutton pops out when the Emergency UPM Off pushbutton on the SSBM Control/Monitor Panel is activated.

To reset the Parallel Capacity/Redundant system:

1.Press the Emergency UPM Off PUSH IN TO RESET pushbutton until it clicks in and remains recessed.

2.The Parallel Capacity/Redundant system is now reset. To restart the Parallel Capacity/Redundant system, follow the procedure at the beginning of this chapter.

10--14

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

 

164201373 Rev. A 092402

Page 104
Image 104
Powerware 9315s manual Resetting the Parallel Capacity/Redundant System after