7.2.3Battery Mode

The UPMs transfers to Battery mode automatically if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the batteries provide emergency DC power that the inverters convert to AC power. When the UPMs switch to Battery mode, the alarm indications depend on the cause and condition of the battery charge. The length of time the system can operate in Battery mode depends on loading and the battery supply capacity.

Figure 7---3 shows the path of electrical power through the Parallel Capacity/Redundant system when operating in Battery mode.

UPM

INPUT

UPM1

BATT

UPM2

BATT

UPM3

BATT

UPM4

BATT

BYPASS

INPUT

SSBM

 

 

FBP

CBP

 

(open)

SS

 

CBS

OUTPUT TO

CRITICAL

LOAD

Path of Electrical Power

Figure 7---3. Path of Current Through the Parallel Capacity/Redundant

System in Battery Mode

When the discharging battery voltage reaches the lower limit of UPM operational capability, the critical load is transferred by the SSBM to Bypass mode, if it is available. If Bypass input is not available, a “Shutdown Imminent” warning occurs. The warning time before critical load loss occurs is approximately 2 minutes, depending on battery capacity and the amount of loading.

If incoming power returns to within specified parameters, the UPMs automatically return to Normal mode and alarm indications clear. However, the process of returning to Normal mode is not instantaneous. The UPMs gradually draw increasing power from the incoming utility until Normal mode is achieved.

7--6

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

 

164201373 Rev. A 092402

Page 58
Image 58
Powerware 9315s manual Battery Mode