The SSBM (including Bypass) remains locked off until you reset the EMERGENCY UPM OFF pushbutton.

To restart the UPS after pressing the EMERGENCY UPM OFF pushbutton, follow the procedure “Resetting the Parallel Capacity/Redundant System after Emergency UPM Off”, of this chapter, before starting the system.

NOTE: The Remote SSBM Emergency Power Off (REPO) option functions differently than the SSBM EMERGENCY UPM OFF pushbutton on the SSBM control panel. If activated, the REPO option deenergizes the critical load, powers down the UPMs and opens UPM breakers CB1 and contactor K3. The Remote SSBM Emergency Power (REPO) option is not configurable to transfer the critical load to bypass source if activated.

10.2.11 To Use the SSBM EMERGENCY UPM OFF Pushbutton

1.Raise the clear plastic shield covering the red SSBM EMERGENCY UPM OFF pushbutton on the SSBM Control Panel.

2.Press the EMERGENCY UPM OFF pushbutton.

The breakers and contactors open (you can hear them opening and closing) and the Emergency UPM Off PUSH IN TO RESET pushbutton on the SSBM Control Panel pops out.

10.2.12Resetting the Parallel Capacity/Redundant System after an EMERGENCY UPM OFF

CAUTION:

Do not attempt to restart the system after Emergency UPM Off until the cause

of the emergency has been identified and cleared.

The Emergency UPM Off PUSH IN TO RESET pushbutton is a small white button on the SSBM Control Panel. The PUSH TO RESET pushbutton pops out when the Emergency UPM Off pushbutton on the SSBM Control Panel is activated.

To reset the Parallel Capacity/Redundant system:

1.Press the Emergency UPM Off PUSH IN TO RESET pushbutton until it clicks in and remains recessed.

2.On the UPMs, move the CB1 switches from the center (tripped) position to OFF. The switches should be difficult to move from the TRIPPED position.

3.The Parallel Capacity/Redundant system is now reset. To restart the Parallel Capacity/Redundant system, follow the procedure at the beginning of this Chapter.

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

10--7

164201373 Rev. A 092402

 

Page 97
Image 97
Powerware 9315s manual To Use the Ssbm Emergency UPM OFF Pushbutton