13.5.3Meters Printout (Ctrl + M)

This key sequence prints the current readings of the SSBM system meters. The Input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the kVA, kW, and power factor measurements. The output area shows the same information for the power being output by the SSBM. The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V) and the DC current (I). Figure 13---5 shows a sample Meters printout.

 

 

Uninterruptible Power System

UPS System Normal

 

03 NOV 1997 14:22:45

Alarm:

None

 

 

 

 

 

 

 

Notice:

None

 

 

 

 

 

 

 

 

 

Input

 

Output

 

VAB

VBC

VCA FREQ

VAB

VBC

VCA

FREQ

480

480

480 60.0

480

480

480

60.0

 

IA

IB

IC

IA

IB

IC

 

IN

 

640

640

640

480

480

480

0

 

KVA

KW

PF

 

KVA

KW

 

PF

 

530

505

0.95

 

400

320

0.80

 

 

Bypass

 

Battery

 

VAB

VBC

VCA

 

V

+

 

I

 

480

480

480

 

540

 

 

0

Figure 13---5. System Meters Screen

13.5.4System Information Printout (Ctrl + A)

This key sequence prints a listing of all available serial data. This printout contains the information shown on the Event History Log and Meters screens of the SSBM (both Figures 13---4 and 13---5).

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

13--9

164201373 Rev. A 092402

 

Page 131
Image 131
Powerware 9315s manual Meters Printout Ctrl + M, System Information Printout Ctrl + a