13.6.7Battery Test Setup
If Battery Test Setup is selected from the main menu (option 5), the following menu is displayed:
NOTE: If a message stating “Battery Test Requires Calibration” appears, please notify your service representative for proper calibration.
Battery Test Setup
1.Setup
2.Setup Monthly Battery Test
3.Setup Quarterly Battery Test
4.Cancel Pending Battery Test
5.Display Next Scheduled Battery Test
6.Return to Main Menu
Enter Selection:
This menu allows you to schedule, review schedule, or cancel pending battery tests. The following menu is displayed when
Enter Starting Month
Enter Day of Week, Sunday = 1,
Enter Week of Month
Enter Hour of Test
Enter Minute of Test
NOTE: Follow each entry with <CR>.
<CR> with no entry will return to Battery Test Setup Menu.
Enter the information at the prompt with a carriage return to schedule the battery test.
If entry 4 is selected from the Battery Test Setup menu, you will be prompted to enter “Y” to cancel all pending tests. This selection will only cancel pending tests and will not stop a test currently in progress.
If entry 5 is selected from the Battery Test Setup menu, and if a Battery Test is scheduled, the following menu is displayed:
Next Battery Test Scheduled
WK DAY MON HR:MN 4 FRI MAR 15:34
NOTE: Enter <CR> to return to Battery Test Setup Menu.
If 5 is selected and there are no tests scheduled, the following will be displayed:
No Battery Test Scheduled
Enter <CR> to return to Battery Test Setup Menu
NOTE: The unit will only perform one battery test in any 24 hour period.
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM | |