Table O. UPM
|
|
|
| UPM | Max No. of UPMs Connectable to each SSBM | |||||
|
|
|
| Minimum Conductor Size, 3∅, (1) Neutral, (1) Gnd | (Based on | |||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| Number of | Number and |
|
|
| |
| 9315 | Output | Output | Conductor Size | Conductors per | Size of Conduit |
|
|
| |
Model - kVA/kW | Voltage | Current | (AWG or kcmil) | ∅ and Neutral | (in inches) | Model 2500 | Model 3000 | Model 4000 | ||
|
|
|
|
|
|
|
|
|
|
|
200 | 400 | 290 | 4/0 | 2 | 2 | 2.0 | 7 | 7 | 7 | |
225 | 208 | 625 | 350 | 3 | 3 | 2.0 | 4 | 4 | 4 | |
225 | 480 | 271 | 3/0 | 2 | 1 | 2.0 | 7 | 7 | 7 | |
|
|
|
|
|
|
|
|
|
|
|
300 | 480 | 271 | 3/0 | 2 | 1 | 2.0 | 7 | 7 | 7 | |
|
|
|
|
|
|
|
|
|
|
|
300 | 600 | 217 | 350 | 1 | 1 | 2.0 | 8 | 8 | 8 | |
300 | 208 | 830 | 500* | 3 | 3 | 3.0 | 4 | 4 | 4 | |
|
|
|
|
|
|
|
|
|
|
|
300 | 480 | 360 | 250 | 2 | 2 | 2.0 | 7 | 7 | 7 | |
|
|
|
|
|
|
|
|
|
|
|
300 | 600 | 289 | 4/0 | 2 | 2 | 2.0 | 7 | 7 | 7 | |
250 | 400 | 290 | 4/0 | 2 | 2 | 2.0 | 7 | 7 | 7 | |
250 | 400 | 360 | 250 | 2 | 2 | 2.0 | 7 | 7 | 7 | |
|
|
|
|
|
|
|
|
|
|
|
400 | 400 | 433 | 3/0 | 3 | 3 | 2.5 | 4 | 4 | 4 | |
|
|
|
|
|
|
|
|
|
|
|
400 | 400 | 577 | 250 | 3 | 3 | 2.5 | 4 | 4 | 4 | |
500 | 208 | 1110 | 600* | 5 | 5 | 3.0 | 2 | 2 | 2 | |
|
|
|
|
|
|
|
|
|
|
|
500 | 480 | 480 | 250 | 3 | 3 | 3.0 | 4 | 4 | 4 | |
|
|
|
|
|
|
|
|
|
|
|
500 | 480 | 601 | 350 | 3 | 3 | 3.0 | 4 | 4 | 4 | |
500 | 600 | 601 | 350 | 3 | 3 | 3.0 | 4 | 4 | 4 | |
625 | 400 | 722 | 300 | 4 | 3 | 3.0 | 3 | 3 | 3 | |
|
|
|
|
|
|
|
|
|
|
|
625 | 400 | 722 | 300 | 4 | 3 | 3.0 | 3 | 3 | 3 | |
|
|
|
|
|
|
|
|
|
|
|
625 | 400 | 902 | 500 | 4 | 3 | 3.5 | 3 | 3 | 3 | |
625 | 400 | 902 | 500 | 4 | 3 | 3.5 | 3 | 3 | 3 | |
|
|
|
|
|
|
|
|
|
|
|
750 | 480 | 752 | 500 | 3 | 3 | 3.0 | 4 | 4 | 4 | |
|
|
|
|
|
|
|
|
|
|
|
750 | 600 | 601 | 350 | 3 | 3 | 3.0 | 4 | 4 | 4 | |
|
|
|
|
|
|
|
|
|
|
|
750 | 480 | 752 | 500 | 3 | 3 | 3.0 | 4 | 4 | 4 | |
750 | 600 | 601 | 350 | 3 | 3 | 3.0 | 4 | 4 | 4 | |
|
|
|
|
|
|
|
|
|
|
|
750 | 480 | 902 | 400 | 4 | 3 | 3.5 | 3 | 3 | 3 | |
|
|
|
|
|
|
|
|
|
|
|
750 | 600 | 722 | 500 | 3 | 3 | 3.0 | 4 | 4 | 4 | |
750 | 480 | 902 | 400 | 4 | 3 | 3.5 | 3 | 3 | 3 | |
|
|
|
|
|
|
|
|
|
|
|
750 | 600 | 722 | 500 | 3 | 3 | 3.0 | 4 | 4 | 4 |
NOTES:
1.* = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements between the UPS and its output transformer.
DESCRIPTION: UPM OUTPUT-TO-SSBM CABLE AND
CONDUIT CONFIGURATIONS
DRAWING NO: |
|
|
SHEET: 1 of 2
|
|
|
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM | ||
| 164201373 Rev. A 092402 |