Table O. UPM Output-to-SSBM Cable and Conduit Configurations: Based on UPM Manuals

 

 

 

 

UPM Output-to-SSBM Cable Configuration

Max No. of UPMs Connectable to each SSBM

 

 

 

 

Minimum Conductor Size, 3, (1) Neutral, (1) Gnd

(Based on UPM-to-SSBM Cable Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of

Number and

 

 

 

 

9315

Output

Output

Conductor Size

Conductors per

Size of Conduit

 

 

 

Model - kVA/kW

Voltage

Current

(AWG or kcmil)

and Neutral

(in inches)

Model 2500

Model 3000

Model 4000

 

 

 

 

 

 

 

 

 

 

 

200

--- 200/160

400

290

4/0

2

2 ---

2.0

7

7

7

225

--- 225/180

208

625

350

3

3 ---

2.0

4

4

4

225

--- 225/180

480

271

3/0

2

1 ---

2.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

300

--- 225/180

480

271

3/0

2

1 ---

2.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

300

--- 225/180

600

217

350

1

1 ---

2.0

8

8

8

300

--- 300/240

208

830

500*

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

 

 

 

 

300

--- 300/240

480

360

250

2

2 ---

2.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

300

--- 300/240

600

289

4/0

2

2 ---

2.0

7

7

7

250

--- 200/160

400

290

4/0

2

2 ---

2.0

7

7

7

250

--- 250/200

400

360

250

2

2 ---

2.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

400

--- 300/240

400

433

3/0

3

3 ---

2.5

4

4

4

 

 

 

 

 

 

 

 

 

 

 

400

--- 400/320

400

577

250

3

3 ---

2.5

4

4

4

500

--- 400/320

208

1110

600*

5

5 ---

3.0

2

2

2

 

 

 

 

 

 

 

 

 

 

 

500

--- 400/320

480

480

250

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

 

 

 

 

500

--- 500/400

480

601

350

3

3 ---

3.0

4

4

4

500

--- 500/400

600

601

350

3

3 ---

3.0

4

4

4

625

--- 500/400

400

722

300

4

3 ---

3.0

3

3

3

 

 

 

 

 

 

 

 

 

 

 

625

--- 500/450

400

722

300

4

3 ---

3.0

3

3

3

 

 

 

 

 

 

 

 

 

 

 

625

--- 625/500

400

902

500

4

3 ---

3.5

3

3

3

625

--- 626/562

400

902

500

4

3 ---

3.5

3

3

3

 

 

 

 

 

 

 

 

 

 

 

750

--- 625/500

480

752

500

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

 

 

 

 

750

--- 625/500

600

601

350

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

 

 

 

 

750

--- 625/562

480

752

500

3

3 ---

3.0

4

4

4

750

--- 625/562

600

601

350

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

 

 

 

 

750

--- 750/600

480

902

400

4

3 ---

3.5

3

3

3

 

 

 

 

 

 

 

 

 

 

 

750

--- 750/600

600

722

500

3

3 ---

3.0

4

4

4

750

--- 750/675

480

902

400

4

3 ---

3.5

3

3

3

 

 

 

 

 

 

 

 

 

 

 

750

--- 750/675

600

722

500

3

3 ---

3.0

4

4

4

NOTES:

1.* = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements between the UPS and its output transformer.

DESCRIPTION: UPM OUTPUT-TO-SSBM CABLE AND

CONDUIT CONFIGURATIONS

DRAWING NO:

164201373---14

 

SHEET: 1 of 2

 

 

 

A---44

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

 

164201373 Rev. A 092402

Page 200
Image 200
Powerware 9315s manual Description UPM OUTPUT-TO-SSBM Cable Conduit Configurations, Output