14.5.2Configuring the Modem to Call a Remote Computer

To configure the modem to call a remote computer, perform the following procedure:

NOTE: The brackets ([ ]) in the following steps indicate characters that require keying in prior to pressing [ENTER].

1.Connect the modem to the PC through the serial port as described in the modem manufacturer’s manual .

2.Key in [A], [T], then press [ENTER].

3.Confirm that the modem responds with “OK” or “0” (zero).

NOTE: In steps 4 and 5, the “xxxxxxx” is the phone number of a remote computer. The phone number should include all local line and long distance access numbers needed to dial out. This number is limited to 32 characters. For example, use “9” if needed for an outside line, “1” for long distance + (Area Code) + Number or whatever access codes are needed to dial the call directly. Add a “,” in the number anywhere that a delay is needed. This will cause a one-second delay. More than one delay may be added to the number; for example, enter “AT&Z0=T,9,,1 (Area Code) (Phone Number)”.

4.To program a group one number, key in [A], [T], [&], [Z], [0] (zero), [=], [T], [,], [xxxxxxx], then press [ENTER].

5.To program a group two number, key in [A], [T], [&], [Z], [1], [=], [T], [,], [xxxxxxx], then press [ENTER].

6.Confirm that the modem responds with “OK” or “0” (zero).

7.Key in [A], [T], [&], [W], [0] (zero), then press [ENTER].

9.Confirm that the modem responds with “OK” or “0” (zero).

8.Key in [A], [T], [&], [Y], [0] (zero), then press [ENTER].

9.Confirm that the modem responds with “OK” or “0” (zero).

10.Connect a telephone line to the modem and test the modem by keying in [A], [T], [D], [S], = [0] (zero), then pressing [ENTER].

11.The modem dials the telephone number stored in step 4. (The number is displayed on the terminal screen as it is dialed.) Repeat steps 4 through 9 as necessary to modify the telephone number.

12.Confirm that the modem responds with “1” (one) or ”Connect” when the connection is made.

NOTE: To set up a group one or group two pager number, refer to “Configuring the Modem to Call a Numeric Pager” section of this chapter.