11.5Relay Interface Module
An optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the Parallel Capacity/Redundant system . A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table
Figure 11---2. Relay Interface Module
The RIM can provide these signals:
•UPS AVAILABLE (pins 1 and 12) Contacts are closed when the UPS is offline.
•UPS OFF LINE (pins 3 and 13) Contacts are closed when the UPS is operating in Normal mode.
•UTILITY FAILURE (pins 6 and 15) Contacts are closed when Utility Failure is detected.
•BATTERY WEAK (pins 5 and 14) Contacts are closed when approximately 2 minutes of battery time is remaining, before the critical load is lost.
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM | ||
| 164201373 Rev. A | 092402 |