11.5Relay Interface Module

An optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the Parallel Capacity/Redundant system . A maximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 11---1 for the number of accessories permitted. Figure 11---2 shows the RIM with its four 15-pin connectors labeled J1 through J4.

Figure 11---2. Relay Interface Module

The RIM can provide these signals:

UPS AVAILABLE (pins 1 and 12) Contacts are closed when the UPS is offline.

UPS OFF LINE (pins 3 and 13) Contacts are closed when the UPS is operating in Normal mode.

UTILITY FAILURE (pins 6 and 15) Contacts are closed when Utility Failure is detected.

BATTERY WEAK (pins 5 and 14) Contacts are closed when approximately 2 minutes of battery time is remaining, before the critical load is lost.