Table M. UPM CAN A & CAN B Interface Inputs and Outputs

From

To UPM

Name

Description

SSBM

 

 

 

A1TB1-1

CAN A

CHANNEL A POWERNET --- HIGH

 

J2---3

 

 

 

 

A1TB1-2

CAN A

CHANNEL A POWERNET --- LOW

Channel A connection of PowerNet from

J2---4

SSBM. Used to control and monitor UPMs.

 

 

A1TB1-3

CAN A

CHANNEL A POWERNET --- GND

 

J2---5

 

 

 

 

A1TB7-1

CAN A

CONTROL POWER --- 12VDC

 

J2---1

Control power connection for Channel A

 

 

A1TB7-2

CAN A

CONTROL POWER --- GND

CAN Logic Board from SSBM.

J2---2

 

 

 

 

A1TB1-6

CAN B

CHANNEL B POWERNET --- HIGH

 

J2---3

 

 

 

 

A1TB1-7

CAN B

CHANNEL B POWERNET --- LOW

Channel B connection of PowerNet from

J2---4

SSBM. Used to control and monitor UPMs.

 

 

A1TB1-8

CAN B

CHANNEL B POWERNET --- GND

 

J2---5

 

 

 

 

A1TB7-3

CAN B

CONTROL POWER --- 12VDC

 

J2---1

Control power connection for Channel B

 

 

A1TB7-4

CAN B

CONTROL POWER --- GND

CAN Logic Board from SSBM.

J2---2

 

 

 

 

DESCRIPTION: UPM CAN INTERFACE:

POWERWARE 9315-- 625/750 UPMs

DRAWING NO: 164201373---6

SHEET: 3 of 3

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

A---25

164201373 Rev. A 092402

 