![](/images/new-backgrounds/1188787/18878763x1.webp)
2.4Installing the Powerware Static Switch
Your Switchboard System Bypass Module (SSBM) includes the Powerware static switch shown below.
SSBM Current | Static Switch | Static Switch | Static Switch | Static Switch |
Rating | Current Rating | Type | Manufacturer | Weight kg (lbs) |
|
|
|
|
|
2500A | 2500A | Fully Rated | Powerware | 91 (200) |
|
|
|
|
|
3000 to 4000A | 4000A | Fully Rated | Powerware | 227 (500) |
|
|
|
|
|
2.4.1Installing a Fully Rated Static Switch (2500A or 4000A)
WARNING:
The SSBM should be shut down prior to installing the static switch.
If the SSBM cannot be shut down, transfer the SSBM to Bypass and manually
open the FBP breaker prior to installing the static switch.
If the SSBM is supplied with a System Maintenance Bypass (SMB), transfer the
SSBM to Maintenance Bypass prior to installing the static switch.
Using an adequate lifting device, install the fully rated static switch in the same manner as a drawout circuit breaker.
2.5Installing SSBM or SMB Circuit Breakers
The SSBM and SMB are equipped with General Electric PowerBreakRII drawout circuit breakers.
| Circuit Breaker |
|
|
SSBM | Current Rating | Circuit Breaker | Circuit Breaker |
Current Rating | (100% Rated) | Manufacturer | Weight kg (lbs) |
|
|
|
|
2500A/100 kAIC | 2500A/100 kAIC | General Electric | 110 (242) |
|
|
|
|
3000A/65 kAIC | 3000A/65 kAIC | General Electric | 110 (242) |
|
|
|
|
3000A/100 kAIC | 3000A/100 kAIC | General Electric | 110 (242) |
|
|
|
|
4000A/65 kAIC | 4000A/65 kAIC | General Electric | 138 (304) |
|
|
|
|
4000A/100 kAIC | 4000A/100 kAIC | General Electric | 138 (304) |
|
|
|
|
2.5.1Installing an SSBM or SMB Circuit Breaker
NOTE: The General Electric installation instructions and user’s guides noted below are available at the GE Industrial Systems Publications Library website of http://www.geindustrial.com/cwc/library.
Using an adequate lifting device, install the SSBM and SMB circuit breakers per
instructions in GE Document
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM | |
| 164201373 Rev. A 092402 |