Table J. Customer Interface Panel Inputs and Outputs (Cont’d)
Terminal | TB Pin # | Name | Description | |
Block | ||||
|
|
| ||
| 1 | ON UPS | Contacts used to indicate On UPS status of | |
| 2 | ON UPS RTN | Parallel Capacity/Redundant System | |
|
|
|
| |
| 3 | ON BYPASS | Contacts used to indicate On Bypass status of | |
| 4 | ON BYPASS RTN | Parallel Capacity/Redundant System (See Note 6) | |
|
|
|
| |
TB4 | 5 | RELAY # 1 NC | General purpose NO and NC relay | |
|
| |||
6 | RELAY # 1 NO | |||
| contacts. (See Note 4) | |||
|
|
| ||
| 7 | RELAY # 1 RTN | ||
|
| |||
|
|
|
| |
| 8 | RELAY # 2 NC | General purpose NO and NC relay | |
| 9 | RELAY # 2 NO | ||
| contacts. (See Note 5) | |||
| 10 | RELAY # 2 RTN | ||
|
| |||
| 1 | Bypass ∅ A |
| |
| 2 | Bypass ∅ B |
| |
|
|
|
| |
| 3 | Bypass ∅ C | Sync Reference Voltage for Optional Powerware | |
|
|
| ||
| 4 | Sync Reference ∅ A | ||
| 9315 Sync Control Connections. | |||
TB6 |
|
| ||
5 | Sync Reference ∅ B | Also used for Optional Powerware | ||
|
|
| ||
| 6 | Sync Reference ∅ C | ||
| and | |||
|
|
| ||
| 7 | Output ∅ A | ||
|
| |||
|
|
|
| |
| 8 | Output ∅ B |
| |
|
|
|
| |
| 9 | Output ∅ C |
| |
|
|
|
| |
| 1 | +12VDC |
| |
| 2 | +12VDC RTN |
| |
| 3 | +12VDC |
| |
| 4 | +12VDC RTN | Optional CAN Power Supply Panel (A13) Terminal | |
TB7 | 5 | +12VDC | ||
|
| Block for Powerware 9315 (500 kVA | ||
6 | +12VDC RTN | |||
| Models only | |||
|
|
| ||
| 7 | +12VDC |
| |
|
|
|
| |
| 8 | +12VDC RTN |
| |
|
|
|
| |
| 9 | +12VDC |
| |
|
|
|
| |
| 10 | +12VDC RTN |
|
NOTES:
5.Relay 1 is normally deenergized and is only energized for an alarm condition.
6.Relay 2 is normally energized and is only deenergized for an alarm condition.
7.If the SSBM is setup for a Powerware Sync Control, the ON BYPASS contact is used for Sync Control and is not available for customer use.
DESCRIPTION:
SSBM CUSTOMER INTERFACE PANEL
DRAWING NO: |
|
SHEET: 6 of 6
|
|
|
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM | ||
| 164201373 Rev. A 092402 |