Table P. UPM Output-to-SSBM Cable and Conduit Configurations: For Max Number of UPMs

 

 

 

 

UPM Output-to-SSBM Cable Configuration

Max No. of UPMs Connectable to each SSBM

 

 

 

 

Minimum Conductor Size, 3, (1) Neutral, (1) Gnd

(Based on UPM-to-SSBM Cable Configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of

Number and

 

 

 

 

9315

Output

Output

Conductor Size

Conductors per

Size of Conduit

 

 

 

Model - kVA/kW

Voltage

Current

(AWG or kcmil)

and Neutral

(in inches)

Model 2500

Model 3000

Model 4000

 

 

 

 

 

 

 

 

 

 

 

200

--- 200/160

400

290

500

1

1 ---

3.5

8

8

8

225

--- 225/180

208

625

500

2

2 ---

3.5

7

7

7

225

--- 225/180

480

271

400

1

1 ---

3.0

8

8

8

 

 

 

 

 

 

 

 

 

 

 

300

--- 225/180

480

271

400

1

1 ---

3.0

8

8

8

 

 

 

 

 

 

 

 

 

 

 

300

--- 225/180

600

217

300

1

1 ---

3.0

8

8

8

300

--- 300/240

208

830

400*

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

 

 

 

 

300

--- 300/240

480

360

4/0

2

2 ---

2.5

7

7

7

 

 

 

 

 

 

 

 

 

 

 

300

--- 300/240

600

289

500

1

1 ---

3.5

8

8

8

250

--- 200/160

400

290

500

1

1 ---

3.5

8

8

8

250

--- 250/200

400

360

4/0

2

2 ---

2.5

7

7

7

 

 

 

 

 

 

 

 

 

 

 

400

--- 300/240

400

433

300

2

2 ---

3.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

400

--- 400/320

400

577

500

2

2 ---

3.5

7

7

7

500

--- 400/320

208

1110

500*

4

4 ---

3.5

3

3

3

 

 

 

 

 

 

 

 

 

 

 

500

--- 400/320

480

480

350

2

2 ---

3.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

500

--- 500/400

480

600

500

2

2 ---

3.5

7

7

7

500

--- 500/400

600

480

350

2

2 ---

3.0

7

7

7

625

--- 500/400

400

722

350

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

700

2

2

4.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

--- 500/450

400

722

350

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

700

2

2

4.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

--- 625/500

400

902

500

3

3 ---

3.5

4

4

4

625

--- 626/562

400

902

500

3

3 ---

3.5

4

4

4

 

 

 

 

 

 

 

 

 

 

 

750

--- 625/500

480

752

350

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

700

2

2

4.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

--- 625/500

600

601

500

2

2 ---

3.5

7

7

7

 

 

 

 

 

 

 

 

 

 

 

750

--- 625/562

480

752

350

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

700

2

2

4.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

--- 625/562

600

601

500

2

2 ---

3.5

7

7

7

 

 

 

 

 

 

 

 

 

 

 

750

--- 750/600

480

902

500

3

3 ---

3.5

4

4

4

750

--- 750/600

600

722

350

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

700

2

2

4.0

7

7

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

--- 750/675

480

902

500

3

3 ---

3.5

4

4

4

750

--- 750/675

600

722

350

3

3 ---

3.0

4

4

4

 

 

 

 

 

 

 

700

2

2

4.0

7

7

7

 

 

 

 

NOTES:

1.The cable configurations shown support connection of the maximum number of UPMs for each SSBM model. The maximum number of UPMs connected to any SSBM shall not exceed eight.

2.Maximum conductor size considered: 700 kcmil.

3.* = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements between the UPS and its output transformer.

DESCRIPTION: UPM OUTPUT-TO-SSBM CABLE AND

CONDUIT CONFIGURATIONS

DRAWING NO:

164201373---14

 

SHEET: 2 of 2

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

A---45

164201373 Rev. A 092402

 

Page 201
Image 201
Powerware 9315s manual