Table P. UPM
|
|
|
| UPM | Max No. of UPMs Connectable to each SSBM | ||||||
|
|
|
| Minimum Conductor Size, 3∅, (1) Neutral, (1) Gnd | (Based on | ||||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
| Number of | Number and |
|
|
| ||
| 9315 | Output | Output | Conductor Size | Conductors per | Size of Conduit |
|
|
| ||
Model - kVA/kW | Voltage | Current | (AWG or kcmil) | ∅ and Neutral | (in inches) | Model 2500 | Model 3000 | Model 4000 | |||
|
|
|
|
|
|
|
|
|
|
| |
200 | 400 | 290 | 500 | 1 | 1 | 3.5 | 8 | 8 | 8 | ||
225 | 208 | 625 | 500 | 2 | 2 | 3.5 | 7 | 7 | 7 | ||
225 | 480 | 271 | 400 | 1 | 1 | 3.0 | 8 | 8 | 8 | ||
|
|
|
|
|
|
|
|
|
|
| |
300 | 480 | 271 | 400 | 1 | 1 | 3.0 | 8 | 8 | 8 | ||
|
|
|
|
|
|
|
|
|
|
| |
300 | 600 | 217 | 300 | 1 | 1 | 3.0 | 8 | 8 | 8 | ||
300 | 208 | 830 | 400* | 3 | 3 | 3.0 | 4 | 4 | 4 | ||
|
|
|
|
|
|
|
|
|
|
| |
300 | 480 | 360 | 4/0 | 2 | 2 | 2.5 | 7 | 7 | 7 | ||
|
|
|
|
|
|
|
|
|
|
| |
300 | 600 | 289 | 500 | 1 | 1 | 3.5 | 8 | 8 | 8 | ||
250 | 400 | 290 | 500 | 1 | 1 | 3.5 | 8 | 8 | 8 | ||
250 | 400 | 360 | 4/0 | 2 | 2 | 2.5 | 7 | 7 | 7 | ||
|
|
|
|
|
|
|
|
|
|
| |
400 | 400 | 433 | 300 | 2 | 2 | 3.0 | 7 | 7 | 7 | ||
|
|
|
|
|
|
|
|
|
|
| |
400 | 400 | 577 | 500 | 2 | 2 | 3.5 | 7 | 7 | 7 | ||
500 | 208 | 1110 | 500* | 4 | 4 | 3.5 | 3 | 3 | 3 | ||
|
|
|
|
|
|
|
|
|
|
| |
500 | 480 | 480 | 350 | 2 | 2 | 3.0 | 7 | 7 | 7 | ||
|
|
|
|
|
|
|
|
|
|
| |
500 | 480 | 600 | 500 | 2 | 2 | 3.5 | 7 | 7 | 7 | ||
500 | 600 | 480 | 350 | 2 | 2 | 3.0 | 7 | 7 | 7 | ||
625 | 400 | 722 | 350 | 3 | 3 | 3.0 | 4 | 4 | 4 | ||
|
|
|
|
|
|
| |||||
700 | 2 | 2 | 4.0 | 7 | 7 | 7 | |||||
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |
625 | 400 | 722 | 350 | 3 | 3 | 3.0 | 4 | 4 | 4 | ||
|
|
|
|
|
|
| |||||
700 | 2 | 2 | 4.0 | 7 | 7 | 7 | |||||
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |
625 | 400 | 902 | 500 | 3 | 3 | 3.5 | 4 | 4 | 4 | ||
625 | 400 | 902 | 500 | 3 | 3 | 3.5 | 4 | 4 | 4 | ||
|
|
|
|
|
|
|
|
|
|
| |
750 | 480 | 752 | 350 | 3 | 3 | 3.0 | 4 | 4 | 4 | ||
|
|
|
|
|
|
| |||||
700 | 2 | 2 | 4.0 | 7 | 7 | 7 | |||||
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |
750 | 600 | 601 | 500 | 2 | 2 | 3.5 | 7 | 7 | 7 | ||
|
|
|
|
|
|
|
|
|
|
| |
750 | 480 | 752 | 350 | 3 | 3 | 3.0 | 4 | 4 | 4 | ||
|
|
|
|
|
|
| |||||
700 | 2 | 2 | 4.0 | 7 | 7 | 7 | |||||
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |
750 | 600 | 601 | 500 | 2 | 2 | 3.5 | 7 | 7 | 7 | ||
|
|
|
|
|
|
|
|
|
|
| |
750 | 480 | 902 | 500 | 3 | 3 | 3.5 | 4 | 4 | 4 | ||
750 | 600 | 722 | 350 | 3 | 3 | 3.0 | 4 | 4 | 4 | ||
|
|
|
|
|
|
| |||||
700 | 2 | 2 | 4.0 | 7 | 7 | 7 | |||||
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |
750 | 480 | 902 | 500 | 3 | 3 | 3.5 | 4 | 4 | 4 | ||
750 | 600 | 722 | 350 | 3 | 3 | 3.0 | 4 | 4 | 4 | ||
|
|
|
|
|
|
| |||||
700 | 2 | 2 | 4.0 | 7 | 7 | 7 | |||||
|
|
|
|
NOTES:
1.The cable configurations shown support connection of the maximum number of UPMs for each SSBM model. The maximum number of UPMs connected to any SSBM shall not exceed eight.
2.Maximum conductor size considered: 700 kcmil.
3.* = Connections to output transformer, not UPM. Refer to applicable Powerware 9315 UPS Installation manual for UPS cable requirements between the UPS and its output transformer.
DESCRIPTION: UPM OUTPUT-TO-SSBM CABLE AND
CONDUIT CONFIGURATIONS
DRAWING NO: |
|
|
SHEET: 2 of 2
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM | |
164201373 Rev. A 092402 |
|