Table 13---3 shows which options are available for each port. The sections that follow describe the configuration settings you can change.

Table 13---3.Options Available for Each Communication Port

Port 1

Port 2

Options

 

 

 

X

X

Terminal Mode

 

 

 

 

X

Calibration Mode

 

 

 

X

X

System Configuration

 

 

 

 

X

Computer Mode

 

 

 

X

 

Remote Monitor Mode

 

 

 

X

X

Baud rate of 300, 1200, 2400, 4800, 9600, or 19,200

 

 

 

X

X

Data size/stop bits of 8/1 or 8/2

 

 

 

 

X

Data size/stop bits of 7/1 or 7/2

 

 

 

X

X

Disabled handshaking

 

 

 

X

X

XON/XOFF handshaking

 

 

 

13.4.1Modes

The operational mode of the port. Each communications port operates in one of the following modes:

Terminal mode

System events are logged immediately as they occur.

Calibration

Used only by service personnel.

System Config.

Allows you to set building alarms, battery tests, etc.

 

(Check with your Sales or Service Representative for availability.)

Computer

Provides a proprietary Binary Computer Mode (BCM) Interface

 

for Powerware facility monitoring or network communication via

 

ConnectUPS.

Remote Monitor Sends all system event information to an RMP, RIM, or SCM. Available for Port 1 only.

Port 1 and Port 2 cannot be in the same mode simultaneously; they must always be operating in different modes. The modes are described later in this chapter.

13.4.2Rate

The baud rate of the equipment connected to this port. The baud rate determines the speed of data transferred between the SSBM and the connected equipment. For Remote Monitor mode, the baud rate must be set to 300. All other modes should operate at the highest baud rate available with the connected equipment. 300 baud is not recommended for any mode except Remote Monitor.

You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19,200.