5.2To install a RIM:

1.Securely mount the RIM.

2.Install wiring from the RIM using ½-in. conduit through the cable entry panels in the top of the SSBM control section (refer to the enclosed switchboard vendor drawings for the location of the conduit landing plate).

3.If not already installed, locate the RMP adapter cable assembly (see Figure 5---2) in the spare parts kit. Mate the DB---9 connector on the back of the terminal block to the DB---9 connector (Port 1) on the Customer Interface Panel of the SSBM (refer to Drawing 164201373---4 in Appendix A). Use two screws from the spare parts kit to secure the terminal block bracket to the Customer Interface Panel.

Connect to

Port 1 (DB---9) on

Customer Interface Panel

FUSE

TERMINAL

BLOCK (TB3)

Figure 5---2. Terminal Block Bracket

 

 

 

5--2

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

 

164201373 Rev. A 092402

Page 44
Image 44
Powerware 9315s manual To install a RIM, Terminal Block Bracket