10.2.4Single UPM Shutdown
NOTE: If system is not redundant, UPM cannot be shut down using this procedure.
1.On UPM, turn the MODE switch to BYPASS.
2.On SSBM monitor screen, verify UPS OFF, message appears.
3.Set UPM battery disconnect breaker to open.
4.When UPM Battery Disconnected alarm and notification message is received, open CB1 on UPM. The UPM powers down.
WARNING:
Power is present at UPM CB1 input, until upstream UPM input feeder circuit breaker is opened. Fans and load side of K3 will still have voltage present.
10.2.5SSBM Shutdown to Bypass
1.On SSBM, turn the SYSTEM MODE key switch to BYPASS momentarily.
2.Observe CBS opens and CBP closes.
3.On SSBM monitor screen, verify On Bypass, message appears. System is now on bypass.
4.Set UPM battery disconnect breakers to open.
5.When UPM Battery Disconnected alarm and notification message is received, open CB1 on all UPMs, except the last UPM. The last UPM must be shutdown using the UPM LOAD OFF pushbutton. Refer to “Using the UPM LOAD OFF Pushbutton” in this chapter.
6.To shutdown last UPM, press last UPM LOAD OFF pushbutton.
WARNING:
Power is present at UPM CB1 input, until upstream UPM input feeder circuit breaker is opened. Fans and load side of K3 will still have voltage present.