| E6581090 |
| ■Selection of wiring devices |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| breaker (MCCB) |
| Magnetic contactor |
|
| Overload | relay | ||||
|
| Capacity | of |
| Earth leakage breaker (ELCB) |
| (MC) |
|
| (THR) | |||||
| Voltage | applicable |
| Without reactor | With DC reactor | Without | reactor | With DC reactor | Adjusted |
| |||||
| class | motor |
| Inverter model | Rated | Type | Rated | Type | Rated |
| Rated |
| current | Type | |
|
|
| MCCB / | MCCB / | Type | Type | |||||||||
|
| (kW) |
|
| current | current | current | current |
| (A) | Note1) | ||||
|
|
|
|
| (A) | (ELCB) | (A) | (ELCB) | (A) | Note1) | (A) | Note1) | (For | reference) |
|
|
|
|
|
| Note1) | Note1) |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Single- | 0.1 |
| 5 |
| 9 |
|
| 0.7 | LR3D056 | |||||
| phase | 0.2 |
| 10 | NJ30E | 9 | LC1D096 |
| 1.3 | LR3D066 | |||||
| 100V | 0.4 |
| 15 | (NJV30E) | 9 |
|
| 2.3 | LR3D076 | |||||
| class | 0.75 |
| 30 |
| 18 | LC1D186 |
| 3.6 | LR3D086 | |||||
| Single- | 0.2 |
| 5 |
| 5 |
| 9 |
| 9 |
|
| 1.3 | LR3D066 | |
| 0.4 |
| 10 |
| 5 | NJ30E | 9 | LC1D096 | 9 | LC1D096 |
| 2.3 | LR3D076 | ||
| phase |
| NJ30E |
| |||||||||||
| 0.75 |
| 15 | 10 | 9 |
| 9 |
|
| 3.6 | LR3D086 | ||||
| 200V |
| (NJV30E) | (NJV30E) |
|
|
| ||||||||
| 1.5 |
| 20 | 15 | 18 | LC1D186 | 12 | LC1D126 |
| 6.8 | LR3D126 | ||||
| class |
|
|
|
| ||||||||||
| 2.2 |
| 30 |
| 30 |
| 25 | LC1D256 | 18 | LC1D186 |
| 9.3 | LR3D146 | ||
|
|
|
|
|
| ||||||||||
|
| 0.1 |
| 5 |
| 5 |
| 9 |
| 9 |
|
| 0.7 | LR3D056 | |
| Three- | 0.2 |
| 5 |
| 5 |
| 9 |
| 9 |
|
| 1.3 | LR3D066 | |
| phase | 0.4 |
| 5 | NJ30E | 5 | NJ30E | 9 | LC1D096 | 9 | LC1D096 |
| 2.3 | LR3D076 | |
| 200V | 0.75 |
| 10 | (NJV30E) | 5 | (NJV30E) | 9 |
| 9 |
|
| 3.6 | LR3D086 | |
| class | 1.5 |
| 15 |
| 10 |
| 9 |
| 9 |
|
| 6.8 | LR3D126 | |
|
| 2.2 |
| 20 |
| 15 |
| 12 | LC1D126 | 12 | LC1D126 |
| 9.3 | LR3D146 | |
| Note 1: Produced by Toshiba Schneider Electric Ltd. |
|
|
|
|
|
|
|
| ||||||
| Note 2: Be sure to attach a surge killer to the exciting coil of the relay and the magnetic contactor. |
| |||||||||||||
10 |
| Selection of surge killers for Toshiba magnetic contactors |
|
|
|
|
|
| |||||||
| 200V class: Surge absorbing units are optionally available for Toshiba C11J to C20J |
|
| ||||||||||||
Note 3: When using the auxiliary contacts 2a of the magnetic contactor MC for the control circuit, connect the |
contacts 2a in parallel to increase reliability.
Of the wiring devices listed in the above table, the magnetic contactors (MC) and the overload relays
Magnetic contactor (MC) | Overload relay |
| ||
ESPER Mighty series | Mighty J series | ESPER Mighty series |
| Mighty J series |
C12A | C13J | T11A |
| T13J |
C20A | C20J |
|
|
|