E6581090

 

Selection of wiring devices

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Non-fuse circuit

breaker (MCCB)

 

Magnetic contactor

 

 

Overload

relay

 

 

Capacity

of

 

Earth leakage breaker (ELCB)

 

(MC)

 

 

(THR)

 

Voltage

applicable

 

Without reactor

With DC reactor

Without

reactor

With DC reactor

Adjusted

 

 

class

motor

 

Inverter model

Rated

Type

Rated

Type

Rated

 

Rated

 

current

Type

 

 

 

MCCB /

MCCB /

Type

Type

 

 

(kW)

 

 

current

current

current

current

 

(A)

Note1)

 

 

 

 

 

(A)

(ELCB)

(A)

(ELCB)

(A)

Note1)

(A)

Note1)

(For

reference)

 

 

 

 

 

 

Note1)

Note1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-

0.1

 

VFNC1S-1001P

5

 

---

---

9

 

---

---

 

0.7

LR3D056

 

phase

0.2

 

VFNC1S-1002P

10

NJ30E

---

---

9

LC1D096

---

---

 

1.3

LR3D066

 

100V

0.4

 

VFNC1S-1004P

15

(NJV30E)

---

---

9

 

---

---

 

2.3

LR3D076

 

class

0.75

 

VFNC1S-1007P

30

 

---

---

18

LC1D186

---

---

 

3.6

LR3D086

 

Single-

0.2

 

VFNC1S-2002P(L)

5

 

5

 

9

 

9

 

 

1.3

LR3D066

 

0.4

 

VFNC1S-2004P(L)

10

 

5

NJ30E

9

LC1D096

9

LC1D096

 

2.3

LR3D076

 

phase

 

NJ30E

 

 

0.75

 

VFNC1S-2007P(L)

15

10

9

 

9

 

 

3.6

LR3D086

 

200V

 

(NJV30E)

(NJV30E)

 

 

 

 

1.5

 

VFNC1S-2015P(L)

20

15

18

LC1D186

12

LC1D126

 

6.8

LR3D126

 

class

 

 

 

 

 

2.2

 

VFNC1S-2022P(L)

30

 

30

 

25

LC1D256

18

LC1D186

 

9.3

LR3D146

 

 

 

 

 

 

 

 

0.1

 

VFNC1-2001P

5

 

5

 

9

 

9

 

 

0.7

LR3D056

 

Three-

0.2

 

VFNC1-2002P

5

 

5

 

9

 

9

 

 

1.3

LR3D066

 

phase

0.4

 

VFNC1-2004P

5

NJ30E

5

NJ30E

9

LC1D096

9

LC1D096

 

2.3

LR3D076

 

200V

0.75

 

VFNC1-2007P

10

(NJV30E)

5

(NJV30E)

9

 

9

 

 

3.6

LR3D086

 

class

1.5

 

VFNC1-2015P

15

 

10

 

9

 

9

 

 

6.8

LR3D126

 

 

2.2

 

VFNC1-2022P

20

 

15

 

12

LC1D126

12

LC1D126

 

9.3

LR3D146

 

Note 1: Produced by Toshiba Schneider Electric Ltd.

 

 

 

 

 

 

 

 

 

Note 2: Be sure to attach a surge killer to the exciting coil of the relay and the magnetic contactor.

 

10

 

Selection of surge killers for Toshiba magnetic contactors

 

 

 

 

 

 

 

200V class: Surge absorbing units are optionally available for Toshiba C11J to C20J

 

 

Note 3: When using the auxiliary contacts 2a of the magnetic contactor MC for the control circuit, connect the

contacts 2a in parallel to increase reliability.

Of the wiring devices listed in the above table, the magnetic contactors (MC) and the overload relays (Th-Ry) are intended for use with the Mighty J series. When using the old series (ESPER Mighty series), refer to the table below showing the correspondence between the two series.

Magnetic contactor (MC)

Overload relay

 

ESPER Mighty series

Mighty J series

ESPER Mighty series

 

Mighty J series

C12A

C13J

T11A

 

T13J

C20A

C20J

 

 

 

J-2

Page 111
Image 111
Toshiba VF-nC1 instruction manual Selection of wiring devices, Thr