E6581090
F-2
6
Output frequency [Hz]
Time [sec]
H
Low speed signal output: 4
FM/OUT terminal (H)
FL terminal (H)
ON
OFF
ON
OFF
0
Set frequency
Low speed reverse signal output: 5
FM/OUT terminal (H)
FL terminal (H)
* FM/OUT terminal function selection (HOUN) : 0 (Output frequency)
[Connection diagram]
P15
OUT
Ry
6.1.2 Output of specified speed reach si+gnal (output of arbitrarily set frequency) H : Speed-reach setting frequency (Hz) H : Output termina l selection 1 (FM/OUT) HOUN : FM/OUT terminal functions selection H : Output terminal se lection 3 (FLA, FLB, FLC)
Function
If the output frequency exceeds the H-set frequency ±2.5 Hz, an OFF signal will be put
out.
ڎThe low speed signal output frequency function is assigned by default to the FM/OUT
terminal.
ڎBefore using the FM/OUT terminal, you need to make a selection between meter (PWM)
output and open collector output.
To use th e FM/OUT terminal as an open collector output terminal, set HOUN to -1 (open
collector output).
ڎSignals can be sent to the relay output terminals FLA, FLB and FLC by changing a
parameter setting.
Parameter for specifying a frequency
Title Function Adjustment range Default setting
H Speed-reach setting frequency
(Hz) 0.0HJ (Hz) 0.0
 ■Related parameters
Title Function Adjustment range Default setting
HOUN FM/OUT terminal functions
selection
-1: Open collector output
0:Output frequency
1:Output current
2:Frequency setting
3:Adjustment (current outp ut
fixed at 100%)
4:Adjustment (current outp ut
fixed at 50%)
5:Adjustment (output fixe d at
the max frequency)
6:Adjustment (gain display)
0
H Output terminal selection 1 (FM/OUT) 0~13 (See 6 .2.6 for de tails.) 4
H Output terminal selection 3 (FL) 0~13 (See 6.2.6 for details.) 10
If using the relay with the rated voltage DC12V of operating
coil, the maximum allowable voltage should be higher than
120% of rated voltage, and the maximum ampere value
should not exceed 50mA.
(Operating coil resistance 250 ~ 800 approx.).