E6581090
Warning
•Do not attach devices with
Prohibited | This could cause a fire. |
|
2 ■Preventing radio noise
To prevent electrical interference such as radio noise, separately bundle wires to the main circuit's power terminals (R/L1, S/L2, T/L3) and wires to the motor terminals (U/T1, V/T2, W/T3).
■Control and main power supply
The control power supply and the main circuit power supply for the
If a malfunction or trip causes the main circuit to be shut off, control power will also be shut off. When checking the cause of the malfunction or the trip, use the trip holding retention selection parameter.
■Wiring
•Because the space between the main circuit terminals is small use sleeved pressure terminals for the connections. Connect the terminals so that adjacent terminals do not touch each other.
•For ground terminal use wires of the size that is equivalent to or larger than those given in table 10.1 and always ground the inverter (200V voltage class: D type ground [former type 3 ground]).
Use as large and short a ground wire as possible and wire it as close as possible to the inverter.
•See the table in 10.1 for wire sizes.
•The length of the main circuit wire in 10.1 should be no longer than 30 meters. If the wire is longer than 30 meters, the wire size (diameter) must be increased.
2.2Standard connections
| Danger |
| • Do not connect input power to the output (motor side) terminals (U/T1, V/T2, |
| W/T3). Connecting input power to the output could destroy the inverter or cause a |
Prohibited | fire. |
• Do not connect resistors to DC terminals (across | |
| It could cause a fire. |
| • First shut off input power and wait at least 15 minutes before touching wires on |
| equipment (MCCB) that is connected to inverter power side. |
| Touching the wires before that time could result in electric shock. |
| • Securely connect to ground with a ground wire. |
| If a secure connection to ground is not made, this could cause electric shock or fire |
Be grounded | when a malfunction or leak current occurs. |
|