E6581090
5.8Base frequency
XN : Base frequency 1 (Hz)
• Function
Sets the base frequency in conformance with load specifications or the motor's rated frequency.
Note: This is an important parameter that determines the constant torque control area.
Base frequency voltage
H
Output voltage [V]
0
* A voltage higher than the voltage set with H is applied to the motor at a frequency higher than the base frequency set with XN, even if the H parameter is
set at a voltage lower than the 5 input voltage.
XN | Output frequency (Hz) |
|
■Parameter setting
Title | Function | Adjustment range | Default setting |
XN | Base frequency 1 (Hz) | 25~200 (Hz) | * |
When operating the inverter with RV selected, change the setting of H to the value printed on the rating plate, in addition to the setting of XN.
*The value is changed according to the
60 [Hz] for VFNC1
5.9Selecting control mode
RV : V/F control mode selection
XD : Torque boost 1 (%)
H : Slip frequency gain
• Function
With
x Vector control
* When torque is not produced enough at low speeds, adjust the rotational speed using the torque boost parameter. To correct the slip frequency, use the H parameter (slip correction gain).
■Parameter setting
Title | Function | Adjustment range | Default setting | |
RV | V/F control mode | 0 (1,2): V/F constant | 0 | |
selection | 3: Sensorless vector control | |||
|
|
Follow the steps below to set the RV parameter.
(Example: Setting the V/F control mode selection parameter (RV) to 3 (Vector control))
Key operated | LED display | Operation |
|
| Displays the operation frequency (operation stopped). |
| (When standard monitor display selection H= is set | |
|
| to 0 [operation frequency]). |
ENT | CWJ | The first basic parameter "History (CWJ)" is displayed. |
▲Switch to the control mode selection parameter (RV) by
RV pressing the △ key.
ENT | Press the ENTER key to display the parameter setting. | ||
(Default setting: 0 (V/F)) | |||
|
|
▲Change the setting to 3 (Vector control) by pressing the △
key.
| ENT | ⇔RV | Press the ENTER key to save the new setting. RV and the |
|
| parameter setting “3” are displayed alternately. | |||
|
|
| ||
|
|
|
|
|
|
|
|