E6581090

5.8Base frequency

XN : Base frequency 1 (Hz)

Function

Sets the base frequency in conformance with load specifications or the motor's rated frequency.

Note: This is an important parameter that determines the constant torque control area.

Base frequency voltage

H

Output voltage [V]

0

* A voltage higher than the voltage set with H is applied to the motor at a frequency higher than the base frequency set with XN, even if the H parameter is

set at a voltage lower than the 5 input voltage.

XN

Output frequency (Hz)

 

Parameter setting

Title

Function

Adjustment range

Default setting

XN

Base frequency 1 (Hz)

25200 (Hz)

*

When operating the inverter with RV selected, change the setting of H to the value printed on the rating plate, in addition to the setting of XN.

*The value is changed according to the set-up parameter condition. (VFNC1 (S)-□□□□P-W type)

60 [Hz] for VFNC1 (S)-□□□□Ptype.

5.9Selecting control mode

RV : V/F control mode selection

XD : Torque boost 1 (%)

H : Slip frequency gain

Function

With VF-nC1, the V/F controls shown below can be selected. x V/F constant

x Vector control

* When torque is not produced enough at low speeds, adjust the rotational speed using the torque boost parameter. To correct the slip frequency, use the H parameter (slip correction gain).

Parameter setting

Title

Function

Adjustment range

Default setting

RV

V/F control mode

0 (1,2): V/F constant

0

selection

3: Sensorless vector control

 

 

Follow the steps below to set the RV parameter.

(Example: Setting the V/F control mode selection parameter (RV) to 3 (Vector control))

Key operated

LED display

Operation

 

 

Displays the operation frequency (operation stopped).

 



(When standard monitor display selection H= is set

 

 

to 0 [operation frequency]).

ENT

CWJ

The first basic parameter "History (CWJ)" is displayed.

Switch to the control mode selection parameter (RV) by

RV pressing the key.

ENT



Press the ENTER key to display the parameter setting.

(Default setting: 0 (V/F))

 

 

Change the setting to 3 (Vector control) by pressing the

key.

 

ENT

RV

Press the ENTER key to save the new setting. RV and the

 

 

parameter setting “3” are displayed alternately.

 

 

 

 

 

 

 

 

 

 

 

E-7

Page 59
Image 59
Toshiba VF-nC1 instruction manual Selecting control mode, XN Base frequency 1 Hz