E6581090

Output terminals cannot be switched between sink logic and source logic.

See the figures below for connection to sink logic and source logic terminals.

 

Sink logic

 

2

+Power supply

 

Input

FM/OUT

Source logic

15VDC

P15

Input

FM/OUT

 

Common CC

 

Common

 

 

 

CC

Programmable

Inverter

Programmable

Inverter

controller

controller

 

 

Switching the input terminal logic between sink and source

Input terminals of the VF-nC1 inverter can be switched between sink logic and source logic, using the H parameter.

When switching between sink logic and source logic, do it before connecting cables to inverter’s control circuit terminals. When the confirmation message G or G is displayed after switching between sink logic and source logic, using the H parameter, reset the inverter, using the operation panel, by turning the power off, or by inputting a reset signal from an external control device.

Switching the VI/S3 terminal between logic input and analog input

The VI/S3 terminal of the VF-nC1 inverter can be switched between contact input and analog input by changing a parameter setting. When switching between contact input and analog input, do it before connecting cables to inverter’s control circuit terminals (H).

If switching between contact input and analog input is done after cable connection, the inverter and/or the external device connected might be damaged. Before turning on the inverter, make sure all cables are connected correctly to the control terminals.

When using the VI/S3 terminal as an contact input terminal (sink logic), be sure to insert a resistor* between the P15 and VI/S3 terminals. (Recommended resistance: 4.7k-1/4W).

Switching the FM/OUT terminal between meter output (PWM output) and open collector output

The FM/OUT terminal of the VF-nC1 inverter can be switched between meter output (PWM output) and open collector output.

When switching between meter output (PWM output) and open collector output, do it before connecting an external device to the inverter. After switching from meter output (PWM output) to open collector output, and vice versa, check using the HOUN parameter to be sure that the desired function is assigned to the FM/OUT terminal, and then turn the power off. After the completion of cable connection, turn the power back on. If switching between meter output and open collector output is done after cable connection, the inverter might be damaged.

B-10

Page 36
Image 36
Toshiba VF-nC1 instruction manual Switching the input terminal logic between sink and source