E6581090
H-1
8
8. Monitoring the operation status
8.1 Status monitor mode
In this mode, you can monitor the operation status of the inverter.To disp lay the operation status during normal operation:

Press the key twice.

Setting procedure (eg. operation at 60Hz)
Item
displayed
Key
operated
LED
display
Communication
No. Description

The operation frequency is displayed (during operation).
(When the standard monitor display selection parameter
H is set at 0 [operation frequency])
Parameter
setting
mode
CWJ The first basic parameter "History (CWJ)" is displayed.
Direction of
rotation HTH FE01 The direction of rotation is displayed.
(H : forward run, T : reverse run)
Operation
frequency
command
H FE02 The operation frequency command value is displayed.
Load
current E FE03 The inverter output current (load current) is displayed. (Default
setting : unit %)
Input
voltage [ FE04 The inverter input (DC) voltage is displayed.
(Default setting: unit %)
Output
voltage R FE05 The inverter output voltage is displayed. (Default setting:
unit %)
Torque
current Y FE20 The torque current is displayed in %.
PI feedback F FE22 The PI feedback value is displayed. (Unit: frequency)
Inverter
load factor N FE27 The inverter load factor is displayed in %.
Output
power J FE30 The inverter output power is displayed in %.
Operation
frequency Z FE00 The operation frequency is displayed.
Input
terminal C!! FE06
The ON/OFF status of each of the control signal input terminals
(F, R, S1, S2 and VI/S3) is displayed in bits.
ON:
OFF: _
Output
terminal Q FE07
The ON/OFF status of each of the control signal output
terminals (FM/OUT and FL) is displayed in bits.
ON:
OFF: _
(Continued overleaf)
MON
MON
Note 1
MON
Note 2
Note 3

C

!!

Input terminal
VI/S3
Input terminal S2 Input terminal F
Input terminal R
Input terminal
S1
 
Output terminal FL
Output terminal
FM/OUT

Q



Note 3