| E6581090 | |||
| (Continued) |
|
|
|
|
|
|
| ||
Error |
| Alarm | Problem |
| Possible causes |
| Remedies |
|
|
|
code |
| code |
|
|
| |||||
|
|
|
|
|
|
|
|
| ||
* |
| 0008 | Input phase failure | • | A phase failure occurred in the | • | Check the main circuit input line |
| ||
GRJ |
|
|
|
| input line of the main circuit. |
| for phase failure. |
| ||
|
|
|
| • The inverter may trip because of | • | Enable H (input phase |
| |||
|
|
|
|
| GRJ if switching between |
| failure detection). Set the |
| ||
|
|
|
|
| acceleration and deceleration is |
| H parameter to 0. |
| ||
|
|
|
|
| done in succession at intervals |
|
|
|
|
|
|
|
|
|
| of less than 1 second. |
|
|
|
|
|
QJ |
| 0010 | Overheat | • | The cooling fan does not rotate. | • | Restart the operation by |
| ||
|
|
|
| • | The ambient temperature is too |
| resetting the inverter after it has |
| ||
|
|
|
|
| high. |
| cooled down enough. |
| ||
|
|
|
|
|
| • | The fan requires replacement if |
| ||
|
|
|
|
|
|
| it does not rotate during |
| ||
|
|
|
|
|
|
| operation. |
| ||
|
|
|
|
|
| • | Secure sufficient space around |
| ||
|
|
|
| • | The vent is blocked up. |
| the inverter. |
| ||
|
|
|
| • | A heat generating device is | • | Do not place any heat- |
| ||
|
|
|
|
| installed close to the inverter. |
| generating device near the |
| ||
|
|
|
| • | The thermistor in the unit is |
| inverter. |
| ||
|
|
|
|
| broken. | • | Make a service call. |
| ||
*WR |
| 001E | Undervoltage trip | • | The input voltage (in the main | • | Check the input voltage. |
| ||
|
|
| (main circuit) |
| circuit) is too low. | • | Enable H (undervoltage |
| ||
|
|
|
|
|
|
| trip selection). |
| ||
|
|
|
|
|
| • | To cope with a momentary stop |
| ||
|
|
|
|
|
|
| due to undervoltage, enable |
| ||
|
|
|
|
|
|
| H |
| ||
|
|
|
|
|
|
| and H |
| ||
GH |
| 0022 | Ground fault trip | • | A ground fault occurs in the | • | Check the cable and the motor |
| ||
|
|
| Arm overcurrent |
| output cable or the motor. |
| for ground faults. |
| ||
|
|
|
| • | A main circuit element is | • | Make a service call. |
| ||
|
|
|
|
| defective. |
|
|
|
|
|
G |
| 0011 | Emergency stop | • | During automatic operation or | • | Reset the inverter. |
| ||
|
|
|
|
| remote operation, a stop |
|
|
|
|
|
|
|
|
|
| command is entered from the |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 13 | |
|
|
|
|
| operation panel or a remote |
|
|
|
| |
|
|
|
|
| input device. |
|
|
| ||
|
|
|
|
|
|
|
|
| ||
GTT |
| 0015 | Main unit RAM fault | • | The control RAM is defective. | • | Make a service call. |
| ||
GTT |
| 0016 | Main unit ROM fault | • | The control ROM is defective. | • | Make a service call. |
| ||
GTT |
| 0017 | CPU fault trip | • | The control CPU is defective. | • | Make a service call. |
| ||
GTT |
| 0018 | Remote control | • | An error arises during remote | • | Check the remote control |
| ||
|
|
| error |
| operation. |
| device, cables, etc. |
| ||
GTT |
| 001A | Current defector | •The current detector is defective. | • | Make a service call. |
| |||
|
|
| fault |
|
|
|
|
|
|
|
GGR |
| 0012 | EEPROM fault 1 | • | A data writing error occurs. | • | Turn off the inverter, then turn it |
| ||
|
|
|
|
|
|
| on again. If it does not recover |
| ||
|
|
|
|
|
|
| from the error, make a service |
| ||
|
|
|
|
|
|
| call. |
| ||
GGR |
| 0013 | EEPROM fault 2 | • | Power supply is cut off during | • | Turn the power off temporarily |
| ||
|
|
|
|
| V[R operation and data |
| and turn it back on, and then try |
| ||
|
|
|
|
| writing is aborted. |
| V[R operation again. |
| ||
GGR |
| 0014 | EEPROM fault 3 | • | A data writing error occurs. | • | Turn off the inverter, then turn it |
| ||
|
|
|
|
|
|
| on again. If it does not recover |
| ||
|
|
|
|
|
|
| from the error, make a service |
| ||
|
|
|
|
|
|
| call. |
| ||
* |
| 0032 | Break in analog | • | The signal input via VI/S3 is | • | Check the cables for breaks |
| ||
G |
|
| signal cable |
| below the analog signal |
| and change the setting of |
| ||
|
|
|
|
| detection level set with H. |
| H if no breaks are found. |
|