6

E6581090

F (F: Forward run)

Forward run command

CC

 

S1(MCHG)

Switching to motor 2

S2(THR2)

Switching to thermal 2

R(AD2)

Switching to acceleration/deceleration 2

6.4 Analog signals for frequency setting

6.4.1Setting frequency command characteristics

H

: Analog input/logic input function selection

 

 

: VI/S3 reference point 1 setting (%)

 

: V1/S3 point 1 frequency (Hz)

H

H

 

: VI/S3 reference point 2 setting (%)

 

: V1/S3 point 2 frequency (Hz)

H

H

Function

By changing the setting of H, the function of the VI/S3 terminal can be switched between 0~(5)10Vdc voltage input and 4~20mAdc current input. The H to H parameters are used to adjust the output frequency according to the analog signal (voltage: 0~(5)10Vdc, current: 4~20mAdc) from an external device.

Parameter setting

Title

Function

Adjustment range

Default setting

 

Analog input/logic input

0: Voltage signal input (0~10(5)Vdc)

0

H

1: Current signal input (0(4)~20Adc)

function selection

 

 

2: Contact input

 

H

VI/S3 reference point 1

0100(%)

0

 

setting (%)

 

 

H

VI/S3 point 1 frequency (Hz)

0.0200.0(Hz)

0.0

H

VI/S3 reference point 2

0100(%)

100

 

setting (%)

 

 

H

VI/S3 point 2 frequency (Hz)

0.0200.0(Hz)

*

Note 1: Do not specify the same value for input points 1 and 2. If you do so, the error message “GTT” will be displayed.

*The value is changed according to the set-up parameter condition. (VFNC1 (S)-□□□□P-W type)

80 [Hz] for VFNC1 (S)-□□□□Ptype.

F-8

Page 72