E6581090

6.5Operation frequency

6.5.1Starting frequency

H

: Starting frequency setting (Hz)

Function

The frequency set with the H parameter is put out immediately after the completion of frequency setting.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Starting frequency setting (Hz)

0.510.0(Hz)

0.5

Output frequency [Hz]

 

6

 

Starting frequency setting

 

H

 

0

Time [sec]

 

6.5.2Start/stop control by means of frequency setting signals

H : Operation starting frequency (Hz)

H : Operation starting frequency hysteresis (Hz)

Function

The start/stop of operation can be controlled, by simply using frequency setting signals.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Operation starting frequency

0.0HJ (Hz)

0.0

(Hz)

 

 

 

H

Operation starting frequency

0.0HJ (Hz)

0.0

hysteresis (Hz)

 

 

 

Output frequency [Hz]

HJ

H H

H

H H

The inverter starts to accelerate when the frequency setting signal reaches point B. Deceleration starts when the frequency setting signal falls below point A.

0

A

B

100% Frequency command value

F-10

Page 74
Image 74
Toshiba VF-nC1 instruction manual Operation frequency, Starting frequency  Starting frequency setting Hz