E6581090
6.5Operation frequency
6.5.1Starting frequency
H
: Starting frequency setting (Hz)
• Function
The frequency set with the H parameter is put out immediately after the completion of frequency setting.
[Parameter setting]
Title | Function | Adjustment range | Default setting |
H | Starting frequency setting (Hz) | 0.5~10.0(Hz) | 0.5 |
Output frequency [Hz] |
|
6 |
|
Starting frequency setting |
|
H |
|
0 | Time [sec] |
|
6.5.2Start/stop control by means of frequency setting signals
H : Operation starting frequency (Hz)
H : Operation starting frequency hysteresis (Hz)
• Function
The start/stop of operation can be controlled, by simply using frequency setting signals.
[Parameter setting]
Title | Function | Adjustment range | Default setting | |
H | Operation starting frequency | 0.0~HJ (Hz) | 0.0 | |
(Hz) | ||||
|
|
| ||
H | Operation starting frequency | 0.0~HJ (Hz) | 0.0 | |
hysteresis (Hz) | ||||
|
|
|
Output frequency [Hz]
HJ
H + H
H
H - H
The inverter starts to accelerate when the frequency setting signal reaches point B. Deceleration starts when the frequency setting signal falls below point A.
0 | A | B | 100% Frequency command value |