E6581090
F-10
6
6.5 Operation frequency

6.5.1 Starting frequency

H : Starting freque ncy setting (Hz)

Function
The frequency set with the H parameter is put out immediately after the completion of
frequency setting.
[Parameter setting]
Title FunctionAdjustment range Default setting
H Starting frequency setting (Hz) 0.510.0(Hz) 0.5
Starting frequency setting
H
Output frequency [Hz]
Time [sec]
0

6.5.2 Start/stop control by m eans of frequency setting signals

H : Operation starting frequency (Hz)

H : Operation starting frequency hysteresis ( Hz)

Function

The start/stop of operation can be controlled, by simply using frequency setting signals.

[Parameter setting]
Title Function Adjustme nt range Default setting
H Operation starting frequency
(Hz) 0.0HJ (Hz) 0.0
H Operation starting frequency
hysteresis (Hz) 0.0HJ (Hz) 0.0
0 A B 100%  Frequency command value
H H
H
HH
HJ The inverter starts to accelerate when the
frequency setting signal reaches po int B.
Deceleration starts when the frequency
setting signal falls below point A.
Output frequency [Hz]