Motor 150%-overload time limit : H

Using the H parameter (motor 150%-overload withstanding time), you can set the time (between 10 and 800 seconds) elapsed before an overload trip occurs (QN) when the motor is operated under a load of 150%.

Title

Function

Adjustment range

Default setting

H

Motor 150%-overload time limit

10800 (sec)

300

5.11Preset speed operation (speeds in 15 steps)

UT UT : Preset speed operation frequencies 1~7 (Hz)

H H : Preset speed operation frequencies 8~15

Function

 

 

 

 

 

 

 

 

 

 

 

A maximum of 15 speed steps can be selected just by switching an external contact signal.

5

 

Multi-speed frequencies can be programmed anywhere from the lower limit frequency NN

 

to the upper limit frequency WN.

 

 

 

 

 

 

 

[Setting method]

 

 

 

 

 

 

 

 

 

 

1) Run/stop

 

 

 

 

 

 

 

 

 

 

 

The starting and stopping control is done from the terminal board.

 

 

 

 

 

Title

 

 

Function

Adjustment range

Default setting

 

Setting

 

 

EOQF

 

Command mode

0: Terminal board

1

 

 

0

 

 

 

selection

 

1: Operation panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: If speed commands (analog signal or digital input) are switched in line with preset speed

 

 

operations, select the terminal board using the frequency setting mode selection HOQF.

 

 

 

 

 

 

 

 

 

 

 

See 3) or 5.1

 

2) Preset speed frequency setting

 

 

 

 

 

 

 

 

 

Set the speed (frequency) of the number of steps necessary.

 

 

 

 

 

Setting from speed 1 to speed 7

 

 

 

 

 

 

 

 

 

 

Title

 

Function

Adjustment range

 

Default setting

 

 

 

UTUT

 

Preset speed operation

NNWN (Hz)

 

0.0

 

 

 

 

 

 

 

frequencies 1~7

 

 

 

 

 

 

 

 

Setting from speed

8 to speed 15

 

 

 

 

 

 

 

 

 

 

Title

 

Function

Adjustment range

 

Default setting

 

 

 

HH

Preset speed operation

NNWN (Hz)

 

0.0

 

 

 

 

 

 

 

frequencies 8~15

 

 

 

 

 

 

 

Example of a frequency setting for forward 15-speed operation

Examples of preset speed contact input signals: When the input terminals are placed in sink logic mode

: ON : OFF (Speed commands other than preset speed commands are valid when all are OFF)

 

CC

Terminal

 

 

 

 

 

 

Preset speed

 

 

 

 

 

 

 

S1

 

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

 

S1-CC

 

S2

 

S2-CC

○ ○ - - ○ ○ - - ○ ○ - - ○ ○

 

 

VI/S3

VI/S3-CC

 

RR-CC- - - - - - - ○ ○ ○ ○ ○ ○ ○ ○

Terminal functions are as follows.

 

 

Terminal S1

Input terminal function selection 3 (S1)

H=6 (SS1)

Terminal S2

Input terminal function selection 4 (S2)

H=7

(SS2)

Terminal VI/S3

Terminal VI and input terminal function

H=2 (Contact input)

selection 5 (VI/S3)

H=8 (SS3)

 

Terminal R

Input terminal function selection 2 (R)

H=9 (SS4)

 

 

 

 

 

E-11

 

 

Page 63
Image 63
Toshiba VF-nC1 Preset speed operation speeds in 15 steps, Motor 150%-overload time limit H, Setting method Run/stop