| E6581090 |
|
|
|
| (Continued) |
|
|
|
| ||
|
|
| Error |
| Alarm | Problem |
| Possible causes |
| Remedies |
|
|
| code |
| code |
|
| |||
|
|
|
|
|
|
|
|
| ||
|
|
| QR |
| 000B | Overvoltage during | • | The deceleration time FGE is | • | Increase the deceleration time |
|
|
|
|
|
| deceleration |
| too short. (Regenerative |
| FGE. |
|
|
|
|
|
|
|
| energy is too large.) | • | Enable H (overvoltage |
|
|
|
|
|
|
| • | H (overvoltage limit |
| limit operation). |
|
|
|
|
|
|
|
| operation) is off. | • | Insert a suitable input reactor. |
|
|
|
|
|
|
| • | The input voltage fluctuates |
|
|
|
|
|
|
|
|
|
| abnormally. |
|
|
|
|
|
|
|
|
| ①The power supply has a |
|
| |
|
|
|
|
|
|
|
| capacity of 200kVA or more. |
|
|
|
|
|
|
|
|
| ②A power factor improvement |
|
| |
|
|
|
|
|
|
|
| capacitor is opened or closed. |
|
|
|
|
|
|
|
|
| ③A system using a thyristor is |
|
| |
|
|
|
|
|
|
|
| connected to the same power |
|
|
|
|
|
|
|
|
|
| distribution line. |
|
|
|
|
| QR |
| 000C | Overvoltage during | • | The input voltage fluctuates | • | Insert a suitable input reactor. |
|
|
|
|
|
|
| abnormally. |
|
| |
|
|
|
|
|
| operation | ①The power supply has a |
|
| |
|
|
|
|
|
|
|
| capacity of 200kVA or more. |
|
|
|
|
|
|
|
|
| ②A power factor improvement |
|
| |
|
|
|
|
|
|
|
| capacitor is opened or closed. |
|
|
|
|
|
|
|
|
| ③A system using a thyristor is |
|
| |
|
|
|
|
|
|
|
| connected to the same power |
|
|
|
|
|
|
|
|
|
| distribution line. |
|
|
|
|
|
|
|
|
| • | The motor is in a regenerative |
|
|
|
|
|
|
|
|
|
| state because the load causes |
|
|
|
|
|
|
|
|
|
| the motor to run at a frequency |
|
|
|
|
|
|
|
|
|
| higher than the inverter output |
|
|
|
|
|
|
|
|
|
| frequency. |
|
|
|
|
| QN |
| 000D | Inverter overload | • | The acceleration time ACC is | • | Increase the acceleration time |
|
|
|
|
|
|
|
| too short. |
| CEE. |
|
|
|
|
|
|
| • | The DC braking amount is too | • | Reduce the DC braking amount |
|
|
|
|
|
|
|
| large. |
| H and the DC braking |
|
|
|
|
|
|
|
|
|
| time H. |
13 |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| • | The V/F setting is improper. | • | Check the V/F parameter | |
|
|
|
|
|
|
| • | A restart signal is input to the |
| setting. |
|
|
|
|
|
|
|
| rotating motor after a | • | Use H |
|
|
|
|
|
|
|
| momentary stop, etc. |
| H |
|
|
|
|
|
|
| • | The load is too large. |
| |
|
|
|
|
|
|
|
|
| • | Use an inverter with a larger |
|
|
|
|
|
|
|
|
|
| rating. |
|
|
| QN |
| 000E | Motor overload | • | The V/F setting is improper. | • | Check the V/F parameter |
|
|
|
|
|
|
| • | The motor is locked up. |
| setting. |
|
|
|
|
|
|
| • | • | Check the load (operated | |
|
|
|
|
|
|
|
| performed continuously. |
| machine). |
|
|
|
|
|
|
| • | An excessive load is applied to | • | Adjust QNO to the overload |
|
|
|
|
|
|
|
| the motor during operation. |
| that the motor can withstand |
|
|
|
|
|
|
|
|
|
| during operation in a low speed |
|
|
|
|
|
|
|
|
|
| range. |
| * |
| 0009 | Output phase failure | • | A phase failure occurred in the | • | Check the main circuit output | ||
|
|
| GRJ |
|
|
|
| output line of the main circuit. |
| line, motor, etc., for phase |
|
|
|
|
|
|
|
|
|
| failure. |
|
|
|
|
|
|
|
|
| • | Enable H (Output phase |
|
|
|
|
|
|
|
|
|
| failure detection). |
|
|
|
| (Continued overleaf) |
|
|
|
|