E6581090
9.1.3Compliance with EMC directive
9.1.3.1The model, noise filter inside
(1)
The above mentioned models install EMI noise filter inside. So the conducted and radiated noise can be reduced, optional EMI noise filters are not needed.
(The additional noise filter should be installed, when more effective reduction is required.)
(2)The main cables such as input to the EMI filter and output of the inverter and the signal cables should be shielded, then cable length should be wired as short as possible. The main input cable should be separated from the main output cable, and cables for control signal also should be separated from main cables, not wiring parallel and not bundling, cross the wires where necessary.
(3)Install EMI filter and inverter on the same metal back plate in an inverter panel. The metal back plate or the cubicle must be grounded absolutely, by using short thick wires, separated from the main cables.
(4)Shielded cables should be grounded on the metal back plate in order to reduce the radiated noise from the other cables. It is an effective measure that shielded cables are grounded close to the inverter or/and operation panel or/and EMI filter(less than 10cm).
(5)Installation of the
9 | 【Ex. Countermeasure - main circuit wiring】 |
|
Connect to the | |
power source | |
| Inverter |
| panel |
| (Metal) |
| Grounding |
| plate |
Connect | to |
the control |
Shielded cables
Separate input and output cables.
Do not run input cables
Do not bundle input and output cables.
IM
Fig. 1