E6581090
(2)Setting the frequency using the operation panel (HOQF : )
Set the frequency from the operation panel.
: Moves the frequency up
: Moves the frequency down
| ■Example of operating a run from the panel | |||||
3 | ||||||
| Key operated | LED display | Operation | |||
|
|
|
|
| Displays the operation frequency. | |
|
|
|
| (When standard monitor display selection H= is set to 0 | ||
|
|
|
|
| [operation frequency]) | |
|
| ▲ | ▼ | Set the operation frequency. | ||
|
|
|
|
|
| |
|
|
| ENT | ⇔HE | Press the ENTER key to save the operation frequency setting. | |
|
|
| HE and the frequency are displayed alternately. | |||
|
| ▲ | ▼ | Pressing the △ key or the ▽ key will change the operation | ||
|
| frequency even during operation. | ||||
|
|
|
|
|
*Press the ENTER key after changing the operation frequency, otherwise it will not be saved, although it is displayed.
(3)Setting the frequency using external signals to the terminal board (HOQF : )
■Frequency setting
1) Setting the frequency using external potentiometer
MAX
MIN
P5
VI/S3
CC
*1
:Setting frequency using the potentiometer
★Potentiometer control
Set frequency using the potentiometer
For more detailed information on adjustments, see 6.4.
60Hz Frequency
0 | MAX |
MIN |
*The H parameter (VI/S3 terminal function selection) is used to specify a function for the VI/S3 input terminal. The FCHG parameter (frequency command forced switching) makes it possible to use both the analog input frequency signal and the frequency signal set with the internal potentiometer, which can be switched by activating or deactivating the input terminals.
See 5.1 for details.
*1It is necessary to set the H (=47~50approx.) in case of using the potentiometer with P5.
Note: The current input and voltage input functions cannot be used at the same time.