Toshiba VF-nC1 instruction manual Operation mode parameters, Torque boost parameters

Models: VF-nC1

1 143
Download 143 pages 53.46 Kb
Page 117
Image 117

E6581090

Operation mode parameters

 

Communication

 

 

Minimum setting unit

 

Default

User

 

 

 

Title

Function

Unit

Panel/

Adjustment range

Reference

 

 

No.

setting

setting

 

 

 

 

Communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

0300

PWM carrier

-

-

0:2kHz

5

 

6.9

 

 

 

 

frequency

 

 

1:2kHz (Random

 

 

 

 

 

 

 

 

 

 

mode)

 

 

 

 

 

 

 

 

 

 

2:4kHz

 

 

 

 

 

 

 

 

 

 

3:4kHz (Random

 

 

 

 

 

 

 

 

 

 

mode)

 

 

 

 

 

 

 

 

 

 

4:8kHzauto-reduction

 

 

 

 

 

 

 

 

 

 

mode

 

 

 

 

 

 

 

 

 

 

5:12kHz (auto-

 

 

 

 

 

 

 

 

 

 

reduction mode)

 

 

 

 

 

 

 

 

 

 

6:16kHz (auto-

 

 

 

 

 

 

 

 

 

 

reduction mode)

 

 

 

 

 

H

0301

Auto-restart control

-

-

0:Disabled

0

 

6.10.1

 

 

 

 

selection

 

 

1:At auto-restart after

 

 

 

 

 

 

 

 

 

 

momentary stop

 

 

 

 

 

 

 

 

 

 

2:When turning ST-

 

 

 

 

 

 

 

 

 

 

CC on or off

 

 

 

 

 

 

 

 

 

 

3:At auto-restart after

 

 

 

 

 

 

 

 

 

 

momentary stop or

 

 

 

 

 

 

 

 

 

 

when turning ST-CC

 

 

 

 

 

 

 

 

 

 

on or off

 

 

 

 

 

H

0302

Regenerative power

-

-

0:Disabled

0

 

6.10.2

 

 

 

 

ride-though control

 

 

1:Enabled

 

 

 

 

 

 

 

 

 

 

2:Deceleration stop

 

 

 

 

 

H

0303

Retry selection

Times

1/1

0(OFF),1-10

0

 

6.10.3

 

 

 

 

(Number of times)

 

 

 

 

 

 

 

 

H

0305

Over voltage limit

-

-

0:Disabled

0

 

6.10.4

 

 

 

 

operation

 

 

1:Enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

2:Enabled (forced

 

 

 

 

 

 

 

 

 

shortened

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

deceleration)

 

 

 

 

 

H

0360

PI control

-

-

0: Disabled

0

 

6.11

 

 

 

 

 

 

 

1: Enabled

 

 

 

 

 

H

0362

Proportional (P) gain

-

0.01/0.01

0.01-100.0

0.30

 

6.11

 

 

H

0363

Integral (I) gain

-

0.01/0.01

0.01-100.0

0.20

 

6.11

 

 

Torque boost parameters

Title

Communication

Function

Unit

Minimum setting

Adjustment range

Default

User

Reference

unit Panel/

No.

setting

setting

 

 

 

 

Communication

 

 

 

 

H

0401

Slip frequency gain

%

1/1

0-150

50

 

6.12.1

H

0409

Base frequency

V

1/0.1

50-500

*2

 

6.12.1

 

 

voltage 1

 

 

 

 

 

 

H

0415

Motor rated current

A

0.1/0.1

0.1-50.0

*3

 

6.12.2

H

0416

Motor no-load current

%

1/1

30-80

*3

 

6.12.2

H

0417

Motor rated speed

min-1

1/1

100-12000

*2

 

6.12.2

H

0418

Speed control gain

%

1/1

0-100

40

 

6.12.2

H

0419

Speed control stable

%

1/1

0-100

20

 

6.12.2

 

 

coefficient

 

 

 

 

 

 

*2: The value is changed according to the set-up parameter condition. (VFNC1 (S)-□□□□P-W type)

FH:80, UL80, VL:60, F127:0, F170:60, F171:200, F204:80, F409:200, F417:1710 for VFNC1 (S)-□□□

Ptype.

*3: Parameter values vary depending on the capacity. Refer to page K-8.