E6581090
Reduction in rated load current
When the PWM carrier frequency is set above 4kHz, the rated current needs to be decreased.
VFNC1S- Ambient VFNC1- temperature
| 2001P | 50°C or less |
| 2002P | 50°C or less |
| 2004P | 40°C or less |
| 40 to 50°C | |
|
| |
| 2007P | 40°C or less |
| 40 to 50°C | |
|
| |
| 2015P | 40°C or less |
| 40 to 50°C | |
|
| |
| 2022P | 40°C or less |
| 40 to 50°C | |
|
| |
| 1001P | 50°C or less |
| 1002P | 50°C or less |
| 1004P | 40°C or less |
| 40 to 50°C | |
|
| |
| 1007P | 50°C or less |
| 2002PL | 40°C or less |
| 40 to 50°C | |
|
| |
| 2004PL | 40°C or less |
| 40 to 50°C | |
|
| |
| 2007PL | 40°C or less |
| 40 to 50°C | |
|
| |
| 2015PL | 40°C or less |
| 40 to 50°C | |
|
| |
| 2022PL | 40°C or less |
| 40 to 50°C | |
|
|
| Carrier frequency |
|
|
| ||
4kHz or less | 8kHz | 12kHz | 16kHz |
|
| |
0.7A | 0.7A | 0.7A | 0.7A |
|
| |
1.4A | 1.4A | 1.4A | 1.4A |
|
| |
2.4A | 2.4A | 2.4A | 2.4A |
|
| |
2.4A | 2.4A | 2.4A | 2.2A |
|
| |
4A | 4A | 3.6A | 3A |
|
| |
4A | 3.6A | 3.2A | 2.8A |
|
| |
7.5A | 7.5A | 7.5A | 7.1A |
|
| |
7.5A | 7.5A | 7.1A | 6.3A |
|
| |
10.0A | 9.5A | 8.5A | 7.5A |
|
| |
10.0A | 8.5A | 7.5A | 6.5A |
|
| |
0.7A | 0.7A | 0.7A | 0.7A |
|
| |
1.4A | 1.4A | 1.4A | 1.4A |
|
| |
2.4A | 2.4A | 2.4A | 2.4A |
|
| |
6 | ||||||
2.4A | 2.4A | 2.4A | 2.2A |
| ||
4A | 4A | 4A | 4A |
| ||
| ||||||
1.2A | 1.2A | 1.2A | 1.2A |
|
| |
1.1A | 1.1A | 1.1A | 1.1A |
|
| |
2.3A | 2.3A | 2.3A | 2.3A |
|
| |
2.1A | 2.1A | 2.1A | 2.1A |
|
| |
4A | 3.6A | 3.2A | 2.8A |
|
| |
3.6A | 3.2A | 2.9A | 2.5A |
|
| |
7.5A | 7.5A | 7.5A | 7.1A |
|
| |
6.8A | 6.8A | 6.8A | 6.4A |
|
| |
10.7A | 10.1A | 9.1A | 8A |
|
| |
9.6A | 9.1A | 8.2A | 7.2A |
|
|
• Function
Although the rated current at 4kHz is shown on the rating plate, the PWM carrier frequency is set to 12kHz by default.
Note: In order to protect the inverter, PWM carrier frequency may fall automatically depending on the circumstances even if it is under the derating in accordance with above table.
If using
6.10Trip-less intensification
6.10.1
H
:
Caution
•Stand clear of motors and mechanical equipment.
If the motor stops because of a momentary power failure, the equipment will start suddenly when the power is restored, and could cause injury.
Mandatory • To prevent accidents, attach labels warning that there is the risk of a sudden start in the event of a power failure to all inverters, motors and machines.
• Function
This parameter detects the rotational speed and direction of rotation of the motor during coasting in the event of a momentary power failure, and restarts the motor smoothly as soon as power is restored (motor speed search function). Also, this parameter makes it possible to switch from commercial power operation to inverter operation without stopping the motor.