6.2.6 Changing the function of an output terminal
H
H
:Output terminal selection 1 (OUT/FM)
:Output terminal selection 3 (FLA, FLB, FLC)
• Function
These parameters are used to send various signals from the inverter to an external device. With these parameters allowing selection from among 14 functions for each output terminal, you can design a system with great flexibility.
■How to use
6
Function of FM/OUT: Use the H parameter to set it.
Function of FLA, FLB, FLC: Use the H parameter to set it.
Ry
*1
FLA
FLB
FLC
P15
FM/OUT
FL
*: The function of the FM/OUT terminal can be switched between meter output (PWM) and open collector output. To use the FM/OUT terminal as an open collector output terminal, set HOUN
to
*1 If using the relay with the rated voltage DC12V of operating coil, the maximum allowable voltage should be higher than 120% of rated voltage, and the maximum ampere value should not exceed 50mA.
(Operating coil resistance 250 ~ 800 Ω approx.).
■Setting of output terminal functions
Terminal | Title | Function | Adjustment range | Default setting | |
symbol | |||||
|
|
|
| ||
FM/OUT | H | Output terminal selection 1 | 0~13 | 4 (low speed | |
|
| (FM/OUT) | detection signal) | ||
FL | H | Output terminal selection 3 | (See Section 11.) | 10 (failure FL) | |
|
| (FL) |
|
|
See 2.3 for details. ■Related parameters
| Title | Function | Adjustment range | Default setting |
|
|
|
|
|
| |
|
|
| 0: Output frequency |
|
|
|
|
| 1: Output current |
|
|
|
| FM/OUT terminal | 2: Frequency setting |
|
|
| HOUN | 3: Adjustment (current output fixed at 100%) | 0 |
| |
| functions selection |
| |||
|
|
| 4: Adjustment (current output fixed at 50%) |
|
|
|
|
| 5: Adjustment (output fixed at the max |
|
|
|
|
| frequency) |
|
|
|
|
| 6: Adjustment (gain display) |
|
|
|
|
|
|
|
|
|
|
|
|
|