E6581090

 

4.1.1

How to set a setup parameter

Setup parameter

After you set the basic parameter V[R to  (Initialize to default setting) or the first power, the

inverter will be in setup parameter mode. When the inverter is in this mode, you need to set a setup parameter, as described below, to make the inverter ready for operation.

Set the setup parameter according to the logic for control input signals used and the base frequency

 

of the motor connected. (If you are not sure which setup parameter should be selected among

 

P, R and P and what values should be specified, consult your reseller.)

 

Each setup parameter automatically sets all parameters relating to the logic for control input signals

 

4

used and the base frequency of the motor connected.

 

This parameter setting is needed only for the VFNC1 (S)-□□□□P-W.

 

 

Follow these steps to change the setup parameter [Example: Changing from P to P: sink logic (negative common) and a base frequency of 60Hz]

Key operated

LED display

Operation

 

P

Turn the power on.

 

 

 

▲ ▼

P

Select a parameter among P, R and P, using

the and keys. Select P in this case.

 

 

 

 

Press the ENTER key to confirm your change.

ENT

KP KV

When KP KV is displayed, you can set the setup

 

 

parameter.

 



The operation frequency is displayed (Standby).

 

 

 

You can change this parameter setting. To do so, you need to reset the basic parameter V[R

to  (default setting).

You can also change the parameters in the table below individually even after setting a setup parameter.

The settings of the parameters listed below are changed by the setup parameter.

When you search for I4W parameters, only the parameters in the shaded area will be displayed as changed parameters.

Values set by each setup parameter

Parameters set

P

R

P

 

(Mainly in Asia)

(Mainly in Europe)

(Mainly in North America)

H

0 [Sink logic (negative common)]

100 (Source logic (positive common))

0 [Sink logic (negative common)]

H / H

220 (V)

220 (V)

230 (V)

H

1410 (min-1)

1410 (min-1)

1710 (min-1)

HJ, WN, H

50.0 (Hz)

50.0 (Hz)

60.0 (Hz)

XN / H

50.0 (Hz)

50.0 (Hz)

60.0 (Hz)

D-3

Page 44
Image 44