| E6581090 |
|
2) Setting the frequency using input voltage |
|
| ||
|
| ★Voltage signal |
|
|
+ | VI/S3 | Setting frequency using voltage signals |
| |
| : Voltage signal |
| ||
| on adjustments, see 6.4. |
| ||
- | CC |
| ||
|
|
| ||
|
| 60Hz |
|
|
|
| Frequency |
|
|
|
| 00Vdc | 10Vdc | 3 |
* | The H parameter (VI/S3 terminal function selection) is used to specify a function | |||
| for the VI/S3 input terminal. The FCHG parameter (frequency command forced |
| ||
| switching) makes it possible to use both the analog input frequency signal and the |
| ||
| frequency signal set with the internal potentiometer, which can be switched by |
| ||
| activating or deactivating the input terminals. |
|
| |
| See 5.1 for details. |
|
|
|
Note: The current input and voltage input functions cannot be used at the same time.
3) Setting the frequency using current input (4-20mA)
+
-
VI/S3
CC
★Current signal
| Setting frequency using current signals | ||||
: Current signal | |||||
on adjustments, see 6.4. | |||||
| |||||
|
|
| |||
| 60Hz |
|
|
| |
| Frequency |
|
|
| |
| 0 |
| 4mAdc | 20mAdc | |
|
|
* The H parameter (VI/S3 terminal function selection) is used to specify a function for the VI/S3 input terminal. The FCHG parameter (frequency command forced switching) makes it possible to use both the analog input frequency signal and the frequency signal set with the internal potentiometer, which can be switched by activating or deactivating the input terminals.
See 5.1 for details.
Note: The current input and voltage input functions cannot be used at the same time.
(4) Setting the frequency by serial communications (HOQF : )
The frequency can also be set from a