E6581090

(Continued)

Error

Alarm

Problem

 

Possible causes

 

Remedies

code

code

 

 

 

 

 

 

 

G

0033

CPU

A communications error occurs

Make a service call.

 

 

communications

 

between control CPUs.

 

 

 

 

error

 

 

 

 

G

0034

Excessive torque

The torque boost parameter

Decrease the setting of the

 

 

boosted

 

XD is set too high.

 

torque boost parameter XD

 

 

 

The impedance of the motor is

If no improvement results,

 

 

 

 

too small.

 

contact Toshiba Technical

 

 

 

 

 

 

Support Center.

* With a parameter, you can choose between trip-on and -off.

[Alarm information] Each message in the table is displayed to give a warning but does not cause the inverter to trip.

 

 

 

Error

Problem

 

Possible causes

 

Remedies

 

 

 

code

 

 

 

 

 

 

 

 

QHH

ST terminal OFF

The ST-CC circuit is opened.

Close the ST-CC circuit.

 

 

 

OQHH

Undervoltage in

The supply voltage between R,

Measure the main circuit supply

 

 

 

 

main circuit

 

S and T is under voltage.

 

voltage.

 

 

 

 

 

 

 

 

If the voltage is at a normal

 

 

 

 

 

 

 

 

level, the inverter requires

 

 

 

 

 

 

 

 

repairing.

 

 

 

TVT[

Retry in process

The inverter is in the process of

The inverter is normal if it

 

 

 

 

 

 

retry.

 

restarts after several tens of

 

 

 

 

 

A momentary stop occurred.

 

seconds.

 

 

 

 

 

 

 

 

The inverter restarts

 

 

 

 

 

 

 

 

automatically. Be careful of

 

 

 

 

 

 

 

 

the machine because it may

 

 

 

 

 

 

 

 

suddenly restart.

 

 

 

GTT

Frequency point

The frequency setting signals at

Set the frequency setting

 

 

 

 

setting error

 

points 1 and 2 are set too close

 

signals at points 1 and 2 apart

 

 

 

 

 

 

to each other.

 

from each other.

 

 

 

ENT

Clear command

This message is displayed

Press the STOP key again to

 

 

 

 

acceptable

 

when pressing the STOP key

 

clear the trip.

13

 

 

 

 

 

while an error code is

 

 

 

 

 

 

 

displayed.

 

 

 

 

 

GQHH

Emergency stop

The operation panel is used to

Press the STOP key for an

 

 

 

 

command

 

stop the operation in automatic

 

emergency stop.

 

 

 

 

acceptable

 

control or remote control mode.

 

To cancel the emergency stop,

 

 

 

 

 

 

 

 

press any other key.

 

 

 

JK/NQ

Setting error alarm /

An error is found in a setting

Check whether the setting is

 

 

 

 

An error code and

 

when data is reading or writing.

 

made correctly.

 

 

 

 

data are displayed

 

 

 

 

 

 

 

 

alternately twice

 

 

 

 

 

 

 

 

each.

 

 

 

 

 

 

 

JGCF

Display of first/last

The first or last data item in the

Press the MON key to exit the

 

 

 

GPF

data items

 

CWJ/CWH data group is

 

data group.

 

 

 

 

 

 

displayed.

 

 

 

 

 

FD

DC braking

DC braking in process

The message goes off in several

 

 

 

 

 

 

 

 

tens of seconds if no problem

 

 

 

 

 

 

 

 

occurs. Note)

 

 

 

G

Flowing out of

The numeric value displayed

When a frequency is displayed,

 

 

 

 

excess number of

 

(e.g., frequency) has a larger

 

decrease the setting of H

 

 

 

 

digits

 

number of digits than the

 

(free unit).

 

 

 

 

 

 

display panel. (The number

 

 

 

 

 

 

 

 

next to the E refers to the

 

 

 

 

 

 

 

 

excess number of digits.)

 

 

 

 

 

(Continued overleaf)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 