E6581090
■Table of output terminal functions 1
Function | Code | Function | Action |
|
|
No. |
|
| |||
|
|
|
|
| |
0 | LL | Frequency lower limit | ON : Output frequency higher than NN setting |
|
|
OFF : Output frequency equal to or lower than NN |
|
| |||
|
|
| setting |
|
|
1 | LLN | Inversion of frequency lower limit | Inverse output of LL |
|
|
2 | UL | Frequency upper limit | ON : Output frequency equal to or higher than WN |
|
|
setting |
|
| |||
|
|
| OFF : Output frequency lower than WN setting |
|
|
3 | ULN | Inversion of frequency upper limit | Inverse output of UL |
|
|
|
| ON : Output frequency equal to or higher than |
|
| |
4 | LOW | H setting |
|
| |
|
|
| |||
|
|
| OFF : Output frequency lower than H setting |
|
|
5 | LOWN | Inversion of | Inverse output of LOW |
|
|
|
| signal |
|
|
|
|
| Designated frequency reach | ON : Output frequency within command frequency |
|
|
6 | RCH | ±2.5Hz |
|
| |
signal (completion of |
|
| |||
OFF : Output frequency exceeding command |
|
| |||
|
| acceleration/deceleration) |
|
| |
|
| frequency ±2.5Hz |
|
| |
|
|
|
|
| |
|
| Inversion of designated |
|
|
|
7 | RCHN | frequency reach signal (inversion | Inverse output of RCH |
|
|
|
| of completion of |
|
|
|
|
| acceleration/deceleration) |
|
|
|
8 | RCHF | Set frequency reach signal | ON : Output frequency within H setting ±2.5Hz |
|
|
OFF : Output frequency exceeding H setting |
|
| |||
|
|
| ±2.5Hz |
|
|
9 | RCHFN | Inversion of set frequency reach | Inverse output of RCHF |
|
|
|
| signal |
|
|
|
10 | FL | Failure FL (trip output) | ON : Inverter trips |
|
|
11 | FLN | Inversion of failure FL (inversion | Inverse output of FL |
|
|
|
| of trip output) |
|
| 11 |
12 | OT | ON : Torque current is held above the torque set with |
| ||
H for a period of time longer than that set |
| ||||
|
|
| with H. |
|
|
13 | OTN | Inversion of | Inverse output of OT |
|
|
detection |
|
| |||
|
|
|
|
|