6.14.6 Input phase failure detection
H
: Input phase failure detection mode selection
• Function
This parameter allows you to select a mode of detecting an input ripple voltage in the main circuit capacitor remains very high for a certain period of time, the
inverter will trip and the FL relay will be activated. At the same time, the error message
GRJK will be displayed.
If the power capacity is far larger than the inverter capacity (by more than 200kVA and more
than 10 times), a detection error may occur. If this occurs, install an AC or DC reactor.
If the motor capacity is very small as compared with the inverter capacity, no
failures may be detected.
H= (Disabled)・・・ No tripping (FL relay not activated)
H= (Enabled) ・・・ An
6if the ripple voltage in the main circuit capacitor remains unusually high for a certain period of time. (FL relay activated)
Title | Function | Adjustment range | Default setting | |
H | Input phase failure | 0: Disabled, 1: Enabled | 1 | |
detection mode selection | ||||
|
|
|
6.14.7
H
H
H
:
:
:Output terminal selection 1 (OUT/FM) (H: Output terminal selection 3 (FL))
• Function
An
torque detection time). To put out the signal via the FM/OUT or FL terminal, this function needs
to be assigned to it in advance, using the output terminal function selection parameter.
Title | Function | Adjustment range | Default setting |
H | 0~200(%) | 150 | |
H | 0.00~10.0(sec) | 0.5 | |
H | Output terminal selection 1 (OUT/FM) | 0~13 | 4 |
H | Output terminal selection 3 (FL) | 0~13 | 10 |