E6581090

Shielded cable

Strip the cable and fix it to the metal plate by means

 

 

of a metal saddle for electrical work or equivalent.

9.1.3.2 The models without EMI filters

(1) Shingle-phase 100V class

: VFNC1-1001P to 1007P

 

 

 

Three-phase 200V class

: VFNC1-2001P to 2022P

 

 

 

Shingle-phase 200V class

: VFNC1S-2002P to 2022P

 

 

 

This subsection explains what measures must be taken to satisfy the EMC directive.

 

Insert a recommended EMI filter (Table 2) on the input side of the inverter to reduce radiation

 

and transmission noises. In the combinations listed in Table 2, inverters were checked for

 

conformity with the EMC directive. For inverters used in Japan, it is recommended to use the

 

NF series of noise filters.

 

 

 

 

 

Table 2 lists noise filters recommended for the inverters.

 

 

 

 

Table 2. Recommended EMI filter selection

 

 

 

Voltage class

Inverter

Filter for class A

Filter for class B

 

 

Compliance Motor cable

Compliance Motor cable

 

 

 

 

 

length 20m or less

length 5m or less

 

 

 

VFNC1-2001P

EMFA2006Z

-

 

9

Three-phase

VFNC1-2002P

EMFA2006Z

-

 

VFNC1-2004P

EMFA2006Z

-

 

 

200V class

VFNC1-2007P

EMFA2006Z

-

 

 

 

VFNC1-2015P

EMFA2015Z

-

 

 

 

VFNC1-2022P

EMFA2015Z

-

 

 

 

VFNC1S-2002P

EMFAS2011Z

-

 

 

Single-phase

VFNC1S-2004P

EMFAS2011Z

-

 

 

VFNC1S-2007P

EMFAS2011Z

-

 

 

200V class

 

 

VFNC1S-2015P

EMFAS2025Z

-

 

 

 

 

 

 

VFNC1S-2022P

EMFAS2025Z

-

 

 

Single-phase

VFNC1S-1001P

EMFAS2011Z

-

 

 

VFNC1S-1002P

EMFAS2011Z

-

 

 

100V class

VFNC1S-1004P

EMFAS2011Z

-

 

 

 

VFNC1S-1007P

EMFAS2025Z

-

 

 

Single-phase

VFNC1S-2002PL

With a built-in filter

With a built-in filter

 

 

VFNC1S-2004PL

With a built-in filter

With a built-in filter

 

 

200V class

 

 

VFNC1S-2007PL

With a built-in filter

With a built-in filter

 

 

Built-in filter

 

 

VFNC1S-2015PL

With a built-in filter

With a built-in filter

 

 

type

 

 

VFNC1S-2022PL

With a built-in filter

With a built-in filter

 

 

 

 

 

(2)The main cables such as input to the EMI filter and output of the inverter and the signal cables should be shielded, then cable length should be wired as short as possible. The main input cable should be separated from the main output cable, and cables for control signal also should be separated from main cables, not wiring parallel and not bundling, cross the wires where necessary.

(3)Install EMI filter and inverter on the same metal back plate in an inverter panel. The metal back plate or the cubicle must be grounded absolutely, by using short thick wires, separated from the main cables.

(4)Please separate input cable to EMI filter from output cable as much as possible.

(5)Shielded cables should be grounded on the metal back plate in order to reduce the radiated noise from the other cables. It is an effective measure that shielded cables are grounded close to the inverter or/and operation panel or/and EMI filter(less than 10cm).

I-3

Page 105
Image 105
Toshiba VF-nC1 instruction manual Models without EMI filters, EMFA2006Z, EMFA2015Z, EMFAS2011Z, EMFAS2025Z