6.Extended parameters

Extended parameters are used for sophisticated operation, fine adjustment and other special purposes. Change parameter settings as required. See Table of extended parameters in Section 11.

6.1Output signal-related parameters

6.1.1Low speed signal

H : Low speed signal output frequency (Hz)

H

: Output terminal selection 1

(FM/OUT)

 

: FM/OUT terminal functions selection

HOUN

 

: Output terminal selection 3

(FLA, FLB, FLC)

H

Function

 

 

 

 

 

 

 

 

 

6

 

If the output frequency exceeds the frequency set with H, an ON signal will be put out.

 

This signal can be used as an electromagnetic brake excitation/release signal.

 

 

 

 

 

 

When using a low speed signal for reversing the direction of rotation of the motor, set the

 

 

H parameter (low speed signal output frequency) above 1 kHz.

 

 

 

 

 

 

 

The low

speed signal output frequency function is assigned by

default

to the FM/OUT

 

 

terminal.

 

 

 

 

 

 

 

 

 

 

 

Before using the FM/OUT terminal, you need to make a selection between meter (PWM)

 

 

output and open collector output.

 

 

 

 

 

 

 

 

 

To use the FM/OUT terminal as an open collector output terminal, set HOUN to -1 (open

 

 

collector output).

 

 

 

 

 

 

 

 

 

Signals can be sent to the relay output terminals FLA, FLB and FLC by changing a

 

 

parameter setting.

 

 

 

 

 

 

 

 

[Parameter setting]

 

 

 

 

 

 

 

 

 

Title

 

Function

Adjustment range

 

Default setting

 

 

 

H

Low speed signal output

0.6HJ (Hz)

 

 

0.6

 

 

 

 

 

frequency (Hz)

 

 

 

 

 

 

 

 

 

Related

parameters

 

 

 

 

 

 

 

 

 

Title

 

Function

Adjustment range

 

Default setting

 

 

 

 

 

 

-1: Open collector output

 

 

 

 

 

 

 

 

 

0: Output frequency

 

 

 

 

 

 

 

 

 

 

1: Output current

 

 

 

 

 

 

 

 

 

 

2: Frequency setting

 

 

 

 

 

 

 

 

FM/OUT terminal functions

3: Adjustment (current output

 

0

 

 

 

 

HOUN

fixed at 100%)

 

 

 

 

 

 

 

selection

4: Adjustment (current output

 

 

 

 

 

 

 

 

 

fixed at 50%)

 

 

 

 

 

 

 

 

 

 

5: Adjustment (output fixed at

 

 

 

 

 

 

 

 

the max frequency)

 

 

 

 

 

 

 

 

 

 

6: Adjustment (gain display)

 

 

 

 

 

 

H

Output terminal selection 1 (FM/OUT)

0~13 (See 6.2.6 for details.)

 

4

 

 

 

 

H

Output terminal selection 3 (FL)

0~13 (See 6.2.6 for details.)

 

10

 

 

 

Output terminal setting

 

 

 

 

 

 

 

 

 

The H parameter (output terminal selection 1 (FM/OUT)) is set by default for low speed

 

 

signal (ON signal).

 

 

 

 

 

 

 

 

 

To switch from ON signal to OFF signal, and vice versa, change the output terminal function

 

 

setting.

 

 

 

 

 

 

 

 

 

 

 

[Parameter setting]

 

 

 

 

 

 

 

 

 

Title

 

Function

Adjustment range

 

 

Setting

 

 

 

H

 

Output terminal selection 1

013

 

4 (ON signal) or

 

 

 

 

(FM/OUT)

(See Section 11.)

 

5 (OFF signal)

 

 

 

 

 

 

 

 

 

To output signals to the FLA, FLB and FLC terminals, set the H parameter.

F-1

Page 65
Image 65
Toshiba VF-nC1 Extended parameters, Output signal-related parameters, FM/OUT terminal functions selection,