6.14.9 Analog input disconnection detection

H : Analog input disconnection detection

Function
This parameter is used to detect a break in an analog signal to the VI/S3 terminal. If an analog
signal is below the level set with H for 0.3 seconds (approx.), the inverter will assume the
signal to be broken and it will trip and display the error message “G.” (The Analog input
disconnection detection function is disabled if H is set to 0.0%.)
Title FunctionAdjustment rangeDefault setting
H Analog input
disconnection detection
0: Disabled
1~100% 0
6.15 Operation panel parameters

6.15.1 Prohibiting the change of parameter settings

H : Prohibition of change of parameter settings

Function
This parameter specifies whether parameter setting is changeable or not.
Setting methods
[Parameter setting]
Title FunctionAdjustment range Default setting
H
Prohibition of
change parameter
settings
0~7 (See the explanation below.)
: Permitted_____ EOQF and HOQF settings cannot be changed during operation. (Def ault)
: Prohibited_____All parameters are read/w rite-protected.
: Permitted_____ EOQF and HOQF settings also can be changed during operation.
: Prohibited_____Freq uency can be changed from the operatio n panel but all other
parameters are read/write-protected.
: Permitted_____ The emergency stop function ca nnot be controlled from the operation pane l
and EOQF and HOQF settings cannot be changed during operation.
: Prohibited_____The emergency stop f unction cannot be controlled from the oper ation panel
but all parameters are read/write-protected.
: Permitted_____ The emergency stop function ca nnot be controlled from the operation pane l
and EOQF and HOQF settings also can be changed during operation.
: Prohibited_____The emergency stop f unction cannot be controlled from the operat ion panel,
frequency can be changed on the operation panel, but any other parameters
are write/read-protected.
Note:Some parameters cannot be changed during operation, no matter how H is set. (See
4.1.4.)
Canceling the setting
Only the setting of H can be changed anytime, no matter how it is set.