E6581090
5.3Standard default setting
V[R : Standard setting mode selection
• Function
Allows setting of all parameters to the standard default setting, etc. at one time. (Except the setting of HO)
|
| Title |
| Function |
|
|
|
| Adjustment range |
| Default setting | |
|
|
|
|
|
|
| 0 | : - |
|
|
|
|
|
|
|
| Standard setting |
| 1 | : Default setting 50Hz |
|
| |||
|
| V[R |
| 2 | : Default setting 60Hz |
| 0 | |||||
|
| mode selection |
| 3 | : Default setting |
| ||||||
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
| 4 | : Trip clear |
|
|
| |
5 |
|
|
|
|
|
| 5 | : Cumulative operation time clear |
|
| ||
| ★This function will be displayed as 0 during reading on the right. This previous setting is | |||||||||||
|
| displayed on the left. |
|
|
|
|
|
|
| |||
|
| Ex. | 3 | 0 |
|
|
|
|
|
|
|
|
|
| ★V[R cannot be set during the inverter operating. Always stop the inverter first and then program. | ||||||||||
|
| [Setting values] |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |||||
|
| 50Hz standard setting | (V[R=) |
|
|
|
| |||||
|
| To set the following parameters for a base | frequency of 50Hz, set the V[R parameter to 1. | |||||||||
|
| (This setting does not affect the settings of any other parameters.) |
|
| ||||||||
|
| • Maximum frequency HJ |
| : 50Hz | • Base frequency 1 XN | : 50Hz | ||||||
|
| • Base frequency 2 H |
| : 50Hz | • Upper limit frequency WN : 50Hz | |||||||
|
| • VI/S3 point 2 frequency H : 50Hz | • Motor rated speed H : | |||||||||
|
|
|
|
|
|
| ||||||
|
| 60Hz standard setting | (V[R=) |
|
|
|
| |||||
|
| To set the following parameters for a base | frequency of 60Hz, set the V[R parameter to 2. | |||||||||
|
| (This setting does not affect the settings of any other parameters.) |
|
| ||||||||
|
| • Maximum frequency HJ |
| : 60Hz | • Base frequency 1 XN | : 60Hz | ||||||
|
| • Base frequency 2 H |
| : 60Hz | • Upper limit frequency WN : 60Hz | |||||||
|
| • VI/S3 point 2 frequency H : 60Hz | • Motor rated speed H : |
Default setting (V[R=)
Setting V[R to will return all parameters to the standard values that were programmed at the factory.
☆When 3 is programmed, < KPKV will be displayed for a short time after setting and will then
be erased and displayed the original indication “PQ” (Setup parameter). (Only for VFNC1 (S)-
• FM/OUT terminal functions selection HOUN | • Meter adjustment HO |
• Analog input/logic input function selection H | • Sink/source selection H |
• Free notes H |
|
See 4.1.1 for setting of setup parameters. |
|
Trip clear (V[R=)
Setting V[R to initializes the past four sets of recorded error history data. * (The parameter does not change.)
Cumulative operation time clear (V[R=)
Setting V[R to allows the initial resetting of the cumulative operation time monitor (0 [zero] time).
* (The parameter does not change.)