Site Requirement Guidelines

Chapter 4 Installation and Maintenance

Preparing to Install the SCE 2000 Platform

Site Requirement Guidelines

The environmental monitoring functionality in the SCE 2000 protects the system and components from potential damage from over-voltage and over-temperature conditions. To ensure normal operation and to avoid unnecessary maintenance, plan your site configuration and prepare your site before installation. After installation, make sure the site maintains an ambient temperature of 41°F to 104°F (5°C to 40°C) with short term temperatures ranging from 23°F to 131°F (–5°C to 55°C), and keep the area around the SCE 2000 chassis free from dust.

Planning a proper location for the SCE 2000 and the layout of your equipment rack or wiring closet is essential for successful system operation. Equipment placed too close together or inadequately ventilated can cause system over-heating. In addition, chassis panels made inaccessible by poor equipment placement can make system maintenance difficult.

Airflow

Figure 4-2: Airflow Through the SCE Platform

When you plan the location and layout of your equipment rack or wiring closet you need to consider how air flows though your system. The SCE 2000 draws cooling air in through the intake vents on the left side of the chassis, moves the air across the internal components, and out through the right side and rear panel of the chassis. The above figure illustrates the airflow through the SCE 2000.

Note Remember to leave a two inch (5 cm) clearance on both sides of the SCE 2000 and five inches (12.7 cm) at the rear for adequate airflow for the inlet and exhaust vents.

Site Requirements

The following tables contain the site requirement specifications for the SCE 2000.

Table 4-2 SCE 2000 Environmental Requirements

 

 

Specification

Acceptable Range

 

 

 

 

 

 

 

 

Temperature -

nominal 41°F to 104°F (5°C to 40°C)

 

 

 

 

 

 

 

Short term temperatures*

23°F to 131°F (-5°C to +55°C)

 

 

 

 

 

 

 

Relative humidity

5% to 95% (non-condensing)

 

 

 

 

 

 

 

Heat dissipation

683 BTU/hour

 

 

 

 

 

 

 

 

 

 

Cisco SCE 2000 4/8xFE Installation and Configuration Guide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OL-7826-05

 

4-3

 

 

 

 

 

 

 

 