Table
Message | Causes | Corrective Actions |
|
|
|
Warning! Power | The system configuration of | If any system components |
required exceeds | processor(s), memory | were just upgraded, return |
PSU wattage. | modules, and expansion | the system to the previous |
Check PSU and | cards may not be supported | configuration. If the system |
system | by the power supplies. | boots without this warning, |
configuration. |
| then the replaced |
Warning! |
| component(s) are not |
| supported with this power | |
Performance |
| |
| supply. If Energy Smart | |
degraded. CPU and |
| |
| power supplies are installed, | |
memory set to |
| |
| replace them with High | |
minimum |
| |
| Output power supplies to use | |
frequencies to |
| |
| the components. See "Power | |
meet PSU wattage. |
| |
| Supplies." | |
System will |
| |
|
| |
reboot. |
|
|
|
|
|
Warning! PSU | A High Output power supply | Install two High Output or |
mismatch. PSU | and an Energy Smart power | two Energy Smart power |
redundancy lost. | supply are installed in the | supplies in the system. |
Check PSU. | system at the same time. | You can also run the system |
|
| |
|
| on one power supply until |
|
| you can obtain two power |
|
| supplies of the same type. |
|
| See "Troubleshooting Power |
|
| Supplies." |
|
|
|
Warning! | Invalid memory | Ensure that the memory |
Unsupported | configuration. The system | modules are installed in a |
memory | will run but with reduced | valid configuration. See |
configuration | functionality. | "General Memory Module |
detected. The |
| Installation Guidelines." If |
memory |
| the problem persists, see |
configuration is |
| "Troubleshooting System |
not optimal. The |
| Memory." |
recommended |
|
|
memory |
|
|
configuration |
|
|
is: <message> |
|
|