4.2.3Servo ON (Output)

(1)Function

The signal outputs to the external device that the power to the robot motor is turned ON.

(2)Terminal number

No. 10 of connector CN10.

(3)Usage

Executing CAL from the external device or starting the program requires the power to the motor to be turned ON. This signal is used to confirm that the power to the motor is turned ON and to light the motor power ON indicator lamp on an external operating panel.

(4)ON conditions

The signal will be turned ON when the power to the motor is turned ON under the following conditions.

The MOTOR switch on the operating panel or the teach pendant is activated.

MOTOR POWER ON + OPERATION PREPARATION START signals are input from the external device.

(5)OFF conditions

The signal will be turned OFF when the power to the motor is turned OFF under the following conditions.

The MOTOR switch of the operating panel or the teach pendant is deactivated and the ROBOT STOP button is operated.

ROBOT STOP is input from the external device.

ƒROBOT FAILURE is outputted. If any of errors 0 6071 to 607B, 0 6671 to 667B, 0 607F occurs, the servo ON signal will be turned OFF in External Auto mode but will not be turned OFF in manual or teach check mode.

When the MOTOR button of the operating panel or the teach pendant is turned ON.

￿MOTORu ￿ ONv ‘ ￿€ ì

When MOTOR POWER ON and OPERATION PREPARATION START

signals are input from the external device.

Servo ON output

When the MOTOR button of the operating panel or the teach pendant is turned OFF and the ROBOT STOP button is operated.

￿ MOTORu ￿ OFv F

When a ROBOT STOP signal is input from an external device.

When a ROBOT FAILURE occurs.

Servo ON Output

72

Page 92
Image 92
Denso RC5 manual ⋅ MOTORu OFv F