ARENA / RANGER

Security Settings page of iLON 10

iLON 10 Setting

ARENA Setting

Allow HTTP Access

-

 

 

HTTP Access -> User Name

iLON 10 Settings -> User Name

 

 

HTTP Access -> Password

iLON 10 Settings -> Password

 

 

Enable Ethernet Connections

-

 

 

Use PPP as dial backup when

-

Ethernet link fails

 

 

 

Enable Outbound PPP Calls

-

 

 

Number of retries for outbound PPP

-

connections

 

Use PAP (after CHAP fails)

-

 

 

Allow and authenticate incoming PPP

-

connections

 

 

 

User Name (for incoming PPP

Outgoing Connection -> User Name

connections)

 

 

 

Password (for incoming PPP

Outgoing Connection -> Password

connections)

 

 

 

Answer phone after X rings

-

USER GUIDE

Hayes AT command set.

Comment

Has to be enabled to allow configuration changes.

Used to authenticate ARENA when it tries to do configuration changes on the iLON 10.

Used to authenticate ARENA when it tries to do configuration changes on the iLON 10.

Has to be enabled for LAN connections and disabled for Dial-up connections.

Has to be enabled in case of Dial-Up. If this setting is unchecked, a dial-out is never initiated from iLON 10.

Has to be enabled in case of Dial-Up. If this setting is unchecked, a dial-out is never initiated from iLON 10.

This is the number of Dial-Out attempts the iLON 10 makes in case of an alarm when the ARENA cannot be reached.

The controller will initiate redialing after 5 minutes waiting time. Usually set to 0, because the PANTHER controller does the alarm repeat.

Authentication mechanism to be used when connecting to a PC via a modem. Must be enabled.

Must be enabled in case of Dial-Up. Otherwise, the supervisor PC (ARENA) cannot contact the iLON 10.

Used to authenticate supervisor PC (ARENA) when it tries to contact the iLON 10 for configuration purpose.

Used to authenticate supervisor PC (ARENA) when it tries to contact the iLON 10 for access to controller data

Number of rings the iLON 10 modem waits until it takes a call from the outside. ARENA sets this value to 1 for fastest connect time.

Edit Site Details

1.Show Sites Overview as described in the “Show Sites Overview” section.

2.For the site you want to edit, click Details button or click on site name in the Site Name column. The Site <name of the site> displays showing the site´s details.