Honeywell EN2Z-0906GE51 R0708 manual Cross Reference of iLON 10 Settings and Arena Settings

Models: EN2Z-0906GE51 R0708

1 160
Download 160 pages 8.87 Kb
Page 59
Image 59

USER GUIDEARENA/ RANGER

Cross Reference of iLON 10 Settings and ARENA Settings

ARENA configures the iLON 10 when creating the site (see in “Create Site” section). If the iLON 10 configuration, e.g. user name or password, was changed manually afterwards, the ARENA settings must be changed accordingly. If ARENA settings and the iLON 10 settings are out of sync it may happen that the iLON 10 cannot be contacted anymore. For the accommodation of settings, use the following table.

General Settings page of iLON 10

iLON 10 Setting

ARENA Setting

Comment

IP Address

Outgoing connection: Remote Site IP

Used in LAN scenarios to contact the iLON

 

Address

10. User needs Administrator privilege

Subnet Mask

Outgoing connection: Subnet Mask

Used in LAN scenarios to define the subnet

 

 

to which the iLON 10 is connected.

 

 

User needs Administrator privilege

Gateway Address

Outgoing connection: Gateway

Used in LAN scenarios to resolve

 

Address

addressing if the iLON 10 and the

 

 

supervisor PC are in different subnets.

 

 

Contact the I.T. administrator to get the

 

 

gateway’s IP address.

Explicit message -> Message with

-

Used to send an alarm from the controller

Code From / To

 

to the iLON 10. This has to be set "from 76

 

 

to 76" and the setting has to be enabled.

 

 

Otherwise no alarms will be sent out via

 

 

the iLON 10.

PPPSettings page of iLON 10

iLON 10 Setting

ARENA Setting

Serial Port Baud Rate

-

Local IP Address for incoming calls

-

 

 

Use Static IP Address-> IP Address

-

 

 

 

Profile 1

-> User Name

Incoming Connection->User Name

 

 

 

Profile 1

-> Password

Incoming Connection->Password

 

 

Profile 1-> Phone Number

Incoming Connection -> Local Phone

 

 

Number

 

 

 

Profile 1

-> Disconnect if idle for

-

 

 

 

Profile 1

-> Modem Init String

Incoming Connection -> Advanced

 

 

settings -> Initialization string

 

 

 

Comment

Should be set to 57600

IP Address for PPP connections via modem. This is automatically generated by the ARENA site administration for Dial-Up scenarios.

IP Address for PPP connections via modem. This is automatically generated by ARENA site administration for Dial-Up scenarios.

User Name which the supervisor PC uses to authenticate an incoming call from the iLON 10.

Password which the supervisor PC uses to authenticate an incoming call from the iLON 10.

Phone number under which the supervisor PC can be reached for Dial- Up scenarios.

This time out applies if no LON connection can be made to the alarm receiver (ARENA). This should never happen. A good default would be 120 sec.

Init string which the iLON 10 uses each time it triggers a dial-out via modem. Via the init strings, special modem configurations can be made. Typical examples are:

X0: Do not wait for dial tone

M0 instead M1 to switch off the modem speaker.

A good default string for many modems is E0Q0V1S0=0&C1M1

If you need special settings, consult your modem manual and a description of the

59

EN2Z-0906GE51 R0708

Page 59
Image 59
Honeywell EN2Z-0906GE51 R0708 manual Cross Reference of iLON 10 Settings and Arena Settings