Honeywell EN2Z-0906GE51 R0708 manual Create Remote Site through Arena via TCP/IP

Models: EN2Z-0906GE51 R0708

1 160
Download 160 pages 8.87 Kb
Page 55
Image 55

USER GUIDE

ARENA/ RANGER

Monitoring (Home) Site (A)

If TCP/IP has been selected, continue with step 41 .

If Modem has been selected, continue with step 61 .

If VPN has been selected, continue with step 18.

NOTE:

Only Microsoft VPN connections are supported.

4.Create Remote Site through ARENA via TCP/IP

The following descriptions refer to an Example of a typical scenario of a Supervisor ARENA – Remote ARENA configuration via LAN as shown in the graphic below.

SITE Configuration Name: represents site B User Name / Password:

must match user name / password of incoming connection of site B

Supervisor ARENA

Site A

Outgoing Connection Incoming Connection

SITE Configuration Name: represents site B User Name / Password:

must match user name / password of outgoing connection of site B

Prevent Supervisor ARENA

 

 

 

from ACCESS and VIEWING

 

LAN

 

through Remote ARENA

MAINTENANCE CALLS

ALARMS

SITE Configuration Name: represents site A User Name / Password:

must match user name / password of outgoing connection of site A

Remote Site (B)

 

SITE Configuration

 

 

 

Incoming Connection Outgoing Connection

Name: represents site A

 

 

 

User Name / Password:

 

 

 

 

must match user name / password

 

 

 

of incoming connection of site A

 

 

Remote ARENA

 

 

 

 

PANTHER / TIGER

PANTHER / TIGER

 

Site B

 

 

 

LON Bus

SERVAL

SERVAL

SERVAL

SERVAL

SERVAL

Fig. 16. System Diagram: Remote Through ARENA via TCP/IP

5.If not already done, select ´TCP/IP` in Connect Through under Outgoing connection to remote site and do the following:

a.In User Name, enter the user name.

b.In Password, enter the password for the user.

NOTES:

User name and password of the supervisor ARENA must match the user name and password under Incoming connection from remote site on the remote ARENA.

On both ARENAs, user name and password must comply with the Windows network requirements. If necessary, please contact the I.T. administrator for detailed information.

This user has not to exist in the user administration of both, Supervisor ARENA and remote ARENA.

c.In Remote Site Address or IP Address, enter the URL or the IP Address of the remote ARENA PC.

d.Under Connect, select Directly if you want to connect to the remote ARENA without an ISP (Internet Service Provider). Select Dial to ISP first using if you want to connect via ISP (dial-up). From the list, select the ISP. If desired

add or remove ISP connections using the buttons. To edit ISP

properties, click button and change properties in the Connection Settings dialog box.

55

EN2Z-0906GE51 R0708

Page 55
Image 55