ARENA / RANGER

USER GUIDE

b.In Destination, select the destination to which the alarms should be forwarded.

c.Check Enabled if the forwarding should be active and check the days on which the triggered alarms should be forwarded to the selected destination.

d.Enter the time range for each day.

4.Click the Advanced tab.

Advanced Tab Settings

a.Check Delay notification if the alarms should be forwarded when the alarm buffer has reached the number of alarms entered in Buffer.

b.In Buffer, enter the number of alarms after which the alarms should be sent.

c.Check Only send alarm if not yet cleared if the alarm should only be forwarded if it is not cleared. .

Uncheck Only send alarm if not yet cleared if a cleared alarm should also be sent.

d.Check Only send alarm if not yet acknowledged if the alarm should only be forwarded if it is not cleared.

Uncheck Only send alarm if not yet acknowledged if an acknowledged alarm should also be sent.

e.In Notification type, select the point when the alarms are sent after the alarm buffer is full:

Immediately

Never

Next connection

f.Select Infinite if ARENA should attempt to forward the alarm forever until forwarding is successful.

g.Select Limited to … days if ARENA should stop forwarding the alarm after the number of days entered.

5.Click OK button.

EN2Z-0906GE51 R0708

92

Page 92
Image 92
Honeywell EN2Z-0906GE51 R0708 manual Advanced Tab Settings