USER GUIDE

ARENA/ RANGER

a.In Arena, select the remote ARENA you want to forward the alarms.

b.In Destination name, enter a descriptive text for the ARENA.

16.Click Advanced tab.

Advanced Tab

Behavior on Connection Failure

a.In Retry count, enter the number of attempts ARENA should make to reach the remote ARENA. When ARENA still cannot reach the remote ARENA after retrying, it stops any further attempt until a new alarm comes in.

b.In Retry interval (minutes), enter interval in minutes the ARENA waits between the retry attempts.

17.Click the OK button.

18.Continue with creating the trigger conditions as described in the “Create Trigger” section.

Create Trigger

A trigger is the condition (event) that causes ARENA to forward an alarm if the condition becomes true.

Example:

If the alarm severity (property) is critical (condition), any critical alarms will be forwarded.

1.Hover the cursor over the Configuration menu icon and click Alarming in the configuration menu.

2.Select the Forwarding tab and click Create new Trigger button, or select the Trigger tab and click Create Trigger button. The Trigger tab displays. Here you create the conditions for triggering the alarm forwarding by doing the following:

89