Figure
I/O VRM
Cover
Knurled Thumbscrew
I/O VRM
Rear Of Chassis
Replacing the I/O VRM
To replace the I/O VRM, follow these steps:
1.Insert the I/O VRM into the socket on the I/O board.
NOTE: The I/O VRM is keyed to fit into the socket in only one direction.
a.Firmly and evenly push on each end of the I/O VRM until it seats into the slot.
b.Ensure that the extraction levers on the socket are in the closed position.
NOTE: You may need to manually close the extraction levers on the socket.
2.Place the I/O VRM cover on top of the I/O VRM and turn the knurled thumb screw clockwise until the cover tightens into place on the chassis wall (Figure
3.Replace the top cover. See “Replacing the Top Cover” (page 182).
4.If rack installed, slide the server completely into the rack. See “Inserting the Server into the Rack” (page 180).
5.Reconnect the power cables and power on the server. See “Powering On the Server” (page 94).
Removing and Replacing the Trusted Platform Module
The Trusted Platform Module (TPM) is an optional security component which enhances security capabilities for the server if it is running the
Removing and Replacing the Trusted Platform Module 233