Program Mode | Continued |
|
|
|
| |||
Reset Parameters to Factory Settings |
|
|
|
| ||||
|
| Sometimes it is necessary to restore the parameter values to the factory settings. Follow | ||||||
|
| this procedure to do so. Be sure to change the Level 2 Motor Data block “Motor Rated | ||||||
|
| Amps” to the correct value after this procedure (restored factory setting is 999). | ||||||
|
| Note: All specific application parameters already programmed will be lost when | ||||||
|
| resetting the control to factory settings. |
| |||||
|
| Note: After factory settings are restored, the drive must be | ||||||
|
|
|
|
|
|
|
|
|
Action |
| Description |
|
| Display | Comments | ||
|
|
|
|
|
|
|
|
|
Apply Power |
| Keypad Display shows this |
|
|
|
| Logo display for 5 seconds. | |
|
|
|
| |||||
|
| opening message. |
|
|
|
|
| |
|
| If no faults and programmed for |
|
|
|
|
| Display mode. Stop LED on. |
|
|
|
|
|
| |||
|
|
|
|
| ||||
|
| LOCAL operation. |
|
|
|
|
| |
Press PROG key |
| Enter program mode. |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| ||||
Press Y or B key |
| Scroll to Level 2 Blocks. |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| ||||
Press ENTER key |
| Select Level 2 Blocks. |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| ||||
Press Y or B key |
| Scroll to the Miscellaneous block. |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| ||||
Press ENTER key |
| Select Miscellaneous block. |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| ||||
Press Y key |
| Scroll to Factory Settings |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| ||||
|
| parameter. |
|
|
|
|
| |
Press ENTER key |
| Access Factory Settings |
|
|
|
|
| V represents blinking cursor. |
|
|
|
|
| ||||
|
|
|
| |||||
|
| parameter. |
|
|
|
|
| |
Press Y key |
| Scroll to YES, to choose original |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| ||||
|
| factory settings. |
|
|
|
|
| |
Press ENTER key |
| Restores factory settings. |
|
|
|
|
| “Loading Presets” is first message |
|
|
|
|
| ||||
|
|
|
| |||||
|
|
|
|
|
|
|
| “Operation Done” is next |
Press Y key |
| Scroll to menu exit. |
|
|
|
|
| “No” is displayed last. |
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
| |||
Press ENTER key |
| Return to Level 1 blocks. |
|
|
|
|
| Exit Level 2 blocks. |
|
|
|
|
|
| |||
|
|
|
|
| ||||
Press Y or B key |
| Scroll to Programming exit. |
|
|
|
|
| Exit Programming mode and |
|
|
|
|
|
| |||
|
|
|
|
| ||||
|
|
|
|
|
|
|
| return to Display mode. |
Press ENTER key |
| Return to display mode. |
|
|
|
|
| Display mode. Stop LED on. |
|
|
|
|
|
| |||
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MN722 |